Electrical installation − EMS version
Control terminals
Interfaces RS485/422 PLC
133
EDS84DPS424 EN 5.0
7.6.4
Interfaces RS485/422 PLC
These connections are available with device versions:
ƒ
E84D
D
xxxxxxx
C1C
xxx
ƒ
E84D
E
xxxxxxx
C1C
xxx
ƒ
E84D
F
xxxxxxx
C1C
xxx
ƒ
E84D
L
xxxxxxx
C1C
xxx
ƒ
E84D
P
xxxxxxx
C1C
xxx
X81 − RS485 PLC
Pin
Signal
Description
Data
84DPSO05_8
M12 type, 8−pole sockets, A−coded
1
+24V
24 V supply
In accordance with IEC 61131−2, type 1
3
GND−EXT
Reference potential
2
RxD+
RS485A’
In accordance with ANSI/TIA/EIA−485−A−98
4
RxD−
RS485B’
5
TxD+
RS485A
6
TxD−
RS485B
7
n. c.
Not assigned
−
8
n. c.
X82 − RS422 PLC
Pin
Signal
Description
Data
84DPSO05_8
M12 type, 8−pole sockets, A−coded
1
+24V
24 V supply
In accordance with IEC 61131−2, type 1
3
GND−EXT
Reference potential
2
RxD+
Re
In accordance with ANSI/TIA/EIA−422
4
RxD−
Reception−
5
TxD+
Trans
6
TxD−
Transmission−
7
n. c.
Not assigned
−
8
n. c.
Please observe that the direct coupling of two 8400 protec EMS devices require an external
connection with terminating resistors.
Summary of Contents for 8400 protec
Page 2: ...0Fig 0Tab 0...
Page 190: ...Appendix Declarations and certificates 13 190 EDS84DPS424 EN 5 0...
Page 191: ...Appendix Declarations and certificates 13 191 EDS84DPS424 EN 5 0...
Page 192: ...Appendix Declarations and certificates 13 192 EDS84DPS424 EN 5 0...
Page 193: ...Appendix Declarations and certificates 13 193 EDS84DPS424 EN 5 0...
Page 194: ...Appendix Declarations and certificates 13 194 EDS84DPS424 EN 5 0...