Safety

Safety

Safety

Safety

Safety
All operations must be carried out by
appropriately trained personnel.
Use all lifting facilities provided e.g.

both lifting points, if fitted, or single
lifting point, if fitted*.

Vertical lifting - Prevent uncontrolled rotation.

Lift machine - Do not lift other equipment with motor
lifting points only.

Before installation check for fan cover damage,
shaft
damage, foot/mounting damage, and loose
fasteners. Check nameplate details.

Ensure level mounting surface, balanced mounting,
not misaligned.

Gaskets, and/or sealants, and guards must be
correctly fitted.

Correct belt tension.

Please observe derating rules, see Design Guide

*Note: maximum hand lift is 20 kg below shoulder,
but above ground level.

Max. weights:

-

Frame size 80: 15 kg

-

Frame size 90 & 100: 30 kg

-

Frame size 112: 65 kg

The voltage on the FC motor is
dangerous when the motor is
connected

to mains. Incorrect installation of the FC
motor may lead to material damage or
serious injury or it may be fatal.

Consequently, the instructions in this Quick Setup as
well as national and local rules and safety
regulations
must be complied with.

Touching the electrical parts may be fatal, even after
the mains supply has been disconnected.
Wait at least 4 minutes.

-

Installation must be fused and isolated correctly.

-

Covers and cable entries must be fitted

NB!

NB!

NB!

NB!

NB!
It is the user's or certified electrician's responsibility
to ensure correct earthing and protection in
accordance with applicable national and local
requirements and standards.

Safety regulations

1. The FC motor must be disconnected from mains if repair

work is to be carried out. Check that the mains supply
has been disconnected and that the necessary time has
passed (4 minutes).

2. Correct protective earthing of the equipment must be

established, the user must be protected against supply
voltage, and the motor must be protected against
overload in  accordance with applicable national and local
regulations.

In UL/cUL applications ETR provides class 20, overload
protection in accordance with the NEC

®

.

RCD's (ELCB relays), multiple protective earthing or
earthing can be used as extra protection, provided that
local safety regulations are complied with.

In case of an earth fault, a DC content may develop in 

the

fault current.

If RCD's are used, local regulations must be observed.
Relays must be suitable for protection of 3-phase
equipment with a bridge rectifier and for a brief
discharge on power-up.

3. The earth leakage currents are higher than 3.5 mA

(approx. 7 mA). This means that the FC motor requires a
fixed, permanent installation as well as reinforced
protective earthing.

W

W

W

W

War

ar

ar

ar

arning against unintended start

ning against unintended start

ning against unintended start

ning against unintended start

ning against unintended start

1. The motor can be brought to a stop by means of digital

commands, bus commands, or references, while the FC
motor is connected to mains.
If personal safety considerations make it necessary to
ensure that no unintended start occurs, these stop
functions are not sufficient.

2. While parameters are being changed, the motor may

start.

3. A motor that has been stopped may start if faults occur in

the electronics of the FC motor, or if a temporary overload
or a fault in the supply mains or the motor connection
ceases.

What if the motor does not start?

-

Make sure no parameters have been changed
from initial delivery status (factory setting). Use
the Local Control Panel or serial port to reset to
factory setting.

-

Make sure no STOP command have been
issued by the optional control panel keyboard
(local stop) Control Panel STOP can only be
restarted by the Control Panel START button.

-

Remove lid to check the Light Emitting Diodes
visible through a hole in the inside isolation cover
(See the drawing), follow table below.

Warning:

Extreme care must be taken when

operating the unit with open lid.

Green

Green

Green

Green

Green

Y

Y

Y

Y

Yellow

ellow

ellow

ellow

ellow

Red

Red

Red

Red

Red

Action

Action

Action

Action

Action

LED 302

LED 302

LED 302

LED 302

LED 302

LED 301

LED 301

LED 301

LED 301

LED 301

LED 300

LED 300

LED 300

LED 300

LED 300

OFF

OFF

OFF

Apply power (see point

 

)

ON

OFF

OFF

Apply  start and r

start and r

start and r

start and r

start and refer

efer

efer

efer

eference

ence

ence

ence

ence signals , (see figure 1 and  point

 

)

ON

OFF

ON

Apply  rrrrreset 

eset 

eset 

eset 

eset  signal according to figure 1.

ON

ON

ON

Switch off power until all LED's have turned off. After power on reset signal is
required.

For further information see the design guide and/or PROFIBUS manual.

This Quick Setup gives information on safety and
helps you to get your FCM 300 Series motors
installed and running in factory setting, see fig. 1. For
additional information, please see the Design Guide.

Before you start, please read the safety instructions
on the back of this Quick Setup.

T

T

T

T

Tools for installation

ools for installation

ools for installation

ools for installation

ools for installation

1 cross-point screwdriver
1 large screwdriver
1 small screwdriver
Min. 2 glands:

Gland sizes

FCM 305-330

3X  PG16

FCM 340-375

1X PG21, 2X PG16

1 mains cable
1 control cable

Max. cable cross section

Mains supply cable

4.0 mm

2

/10 AWG

Control cable

1.5 mm

2

/16 AWG

Serial communication cable

1.5 mm

2

/16 AWG