3. Insert the cable of the new thermal sensor into the lower hole
1
in the chassis. Align the two retaining
clips with the two holes
1
and
2
in the chassis. Then, push the two retaining clips into the two holes
until the thermal sensor is secured into place.
1
2
Figure 70. Installing the thermal sensor
4. Connect the thermal sensor cable to the thermal sensor connector on the system board. See “System
SD module
•
“Removing the SD module” on page 81
•
“Installing the SD module” on page 82
Removing the SD module
To remove the SD module, do the following:
1. Prepare your server. See “Preparing your server and removing the server cover” on page 41.
2. Lay the server on its side for easier operation.
3. Locate the SD module. See “Server components” on page 17.
4. Disconnect the SD module cable.
.