230 V ~ electrical connection of the heat pump control unit
Note
■ This connection must be made with a flexible one power cord.
■ This connection must not be blocked. fuse max. 16 A
■ Standard tariff: the lowest tariff with a delivery lock electricity by
the power plant is not possible
■ Recommended flexible power cable: 3 x 1.5 mm
2
■ Flexible power cord recommended with power supply blocked
by EV: 5 x 1.5 mm
2
/
1
)7$+
13(
9+]
/
1
;
Indoor module: Connections overview
*
;
;
;
;
))
;
-
)
)
)
)
;
;
;
)
)
)
)
) ) )
)) - -
;
;
$
;
;
)
)
A
A
BB
CC
D
D
FF
EE
A
- Control module and electrical
connection of DHW instantaneous
water heater
B
- Electrical connection of the
controller heat pump 230 V ~. F1
T fuse 6.3 A
C
- Terminal strips.
X1 Terminals for protective
conductors all belonging
installation components
X2 Neutral terminals all belonging
installation components
D
- Extended installation plate on the
motherboard
E
- Motherboard: F3 T fuse 2,0
F
- Low voltage installation plate