140
EN-114B_f.1294
Heat pumps with 400V~ external unit
HPSO-12/400
+HPSI-09
HPSO-16/400
+HPSI-09
Heating output data according to EN 14511 (A2/W35)
Rated heating output
kW
7
9
Fan speed
obr./
min
800
Power consumption
kW
2,24
2,86
Coefficient of performance ε
(COP) in heating mode
3,31
3,32
Output control
kW
5,5 do 10,0
5,9 do 11,0
Heating output data according to EN 14511
(A7/W35, spread 5 K)
Rated heating output
kW
12
16
Fan speed
rpm
800
Power consumption
kW
2,58
3,60
Coefficient of performance ε
(COP) in heating mode
4,45
4,37
Output control
kW
6,0 do 13,0
7,6 do 16,7
Heating output data according to EN 14511 (A-7/W35)
Rated heating output
kW
7
9
Power consumption
2,71
3,20
Coefficient of performance ε
(COP) in heating mode
2,73
2,72
Output control
kW
3,4 do 9,0
4,0 do 10,6
Cooling performance data according to
EN 14511 (A35/W7, spread 5 K)
HPSO-12/400
+HPSI-09
HPSO-16/400
+HPSI-09
Rated cooling capacity
kW
5
7
Power consumption
2,08
2,60
Energy efficiency ratio EER in
cooling mode
2,48
2,63
Output control
kW
3,7 do 10,3
5,0 do 12,1
Cooling performance data according to EN 14511 (A35/W18, spread 5 K)
Rated cooling capacity
kW
8
9
Fan speed
rpm
800
Power consumption
kW
2,07
2,58
Energy efficiency ratio
EER in cooling mode
3,82
3,61
Output control
kW
4,7 do 14,8
5,3 do 17,0