16
D
- Gravel substrate for easy condensation
F
- Electrical wires connecting the internal module to the external module and sup
-
plying the electrical wire of the external module:
Lay the wires without stress.
G
- Pipe clamping ring with EPDM insert
H
- Tubular fitting for vibration compensation in hot gas line.
We recommend installing a tubular fitting to compensate for vibrations especially
in lines < 5 m.
K
- Electric auxiliary heating of condensate capture bath
Installing the indoor unit
Transport
Avoid damaging the appliance during transportation. Never put weight on top of the
appliance..
Minimum room area in combination with R32 refrigerant.
It is essential to maintain a minimum room area of 3 m
2
.
■
The minimum area of a room can be calculated in a group of rooms.
■
When adding refrigerant due to a longer line refrigerant, there is no need to adjust
the minimum surface area rooms.
■
Strictly observe the maximum filling volume of 1850 g.
Minimum room volume (according to EN 378) in combination with the refrigerant R410A
With the use of a given refrigerant and based on the specified volumes filling, the following
minimum room volume can be determined: 5,7 m
3
.
For cords > 10 m long, is required additional refrigerant. The minimum volume of the
room must be recalculated depending on the additional filling.
The minimum volume of the technical room according to EN 378 depends on the quantity
refrigerant charge and its chemical composition.
V
min
=
m
maks
G