13 Technical data
13.1 General data
Rated supply voltage:
24 V DC (voltage tolerance 19.2 V DC to
30 V DC according to EN 61131-2)
Maximum interruption time of supply voltage:
≤
10 ms (acc. to EN 61131-2)
Power consumption:
9.6 W (400 mA at 24 V DC)
Inrush current:
max. 5.6 A (with limitation of current)
Safety class:
III in accordance with EN 61131-2 and
EN 50178
13.2 Environmental conditions
Operating temperature:
0 °C to 50 °C (32 °F to 122 °F)
Storage temperature:
-20 °C to +70 °C (-4 °F to 158 °F)
Relative humidity (non-condensing):
5 % to 95 %
Vibration resistance (operation):
(IEC 60068-2-6)
10 Hz
≤
f < 57 Hz at 0.15 mm (0.0059 in)
9 Hz
≤
f < 150 Hz with 2 g (0.0044 pound)
Shock resistance (operation):
25 g (0.055 pound) / 11 ms (IEC 60068-2-27)
13.3 Housing
Construction:
Double-walled ABS housing
Withstands grease, oil, lubricants, alcohol, etc.
Flammability class: UL94-V0
Dimensions:
Diameter: 250 mm / 9.84 in
Total height incl. handle: 114 mm / 4.49 in
Protection degree:
IP65
Weight:
1250 g / 2.76 pound (with E-Stop, with key
switch, without handwheel, without override
potentiometer and without cable)
Display:
Type: Graphics-capable color TFT LC display
Size: 6,5“ (132 x 98 mm)
Resolution: VGA 640 x 480 pixels
Representation 65536 colors
Background lighting:
2 CCFT cold cathode tubes, lifetime 50,000
hours at 25°C in continous operation
Touch Screen: analog-resistive
Keypad:
- Membrane keypad with tactile feedback
- Keys laid out for thumb operation
- Left / right-hand operation
- Customer-specific keypad possible