KEB COMBIVERT F4-C
Name: Basis
09.04.99
2
©
KEB Antriebstechnik, 1999
All Rights reserved
Product Description
Summary
Section
Page
Date
Chapter
2.1.7
Unit Sizes 400V-Class (07-17)
1)
From housing size M fuses of Type Ferra Z 6,6 URD xxx must be used.
2)
This data is only valid for units with internal brake transistor (see „2.1.4 Type Code“).
3)
At mains voltage
≥
460V multiply the nominal current with factor 0,86.
4)
These units can be used with one or more braking modules. For more informations cantact KEB.
Inverter Size
07
09
10
12
13
14
15
16
17
Output nominal power
[kVA] 1,8
2,8
4
6,6
8,3
11
17
23
29
Max. rated motor power
[kW] 0,8
1,5
2,2
4
5,5
7,5
11
15
18,5
Output nominal current
[A] 2,6
4,1
5,8
9,5
12
16,5
24
33
42
Max. short-time current
[A] 4,6
7,4
10,4
17,1
21,6
18
30
25
36
49,5
63
OC-tripping current
[A] 5,7
9
12,7
20,9
26,4
22
36
30
43,2
59,4
75,6
Nominal input current
[A] 2,8
4,5
6,4
10,5
13,2
18,1
26,5
36,5
46
Housing size
D
D
D
D
D
E
D
E
G
E
G
E
G
H
G
H
G
H
R
Rated operating frequency
[kHz]
4
4
4
12
4
16
2
16
8
16
4
8
16
8
16
4
8
16
Max.operating frequency
[kHz]
4
4
4
12
4
16
4
16
16
16
12
16
16
16
16
16
16
16
Power loss at nominal operating
[W]
45
60
80
130 115 180 135 240 200 240 260 260 290 360 310 490 360 470 700
Stall current at 8kHz
[A]
-
-
-
6,4
-
9,5
-
12
19
17
19
-
19
25
22
33
-
30
42
Stall current at 16kHz
[A]
-
-
-
-
-
9,5
-
12
12
-
12
-
8,5
15
9,7
20
-
14
30
Max. heat sink temperatureT
OH
[°C]
85
79
85
73
79
73
90
73
90
73
90
90
90
79
Max. permissible mains fuse (inert)
1)
[A]
10
10
20
20
25
35
50
63
Line cross section
[mm²]
1,5
1,5
2,5
2,5
4
6
10
16
Min. braking resistor
2)
[
Ω
]
160
160
82
50
82
50
39
50
39
39
22
25
22
25
22
9
Typ. braking resistor
2)
[
Ω
]
390
270
150
100
82
56
39
28
Max. braking current
[A]
5
10
15
10
15
21
15
21
21
37
30
37
30
37
88
Tightening torque for terminals
[Nm]
0,5
1,2
0,5
1,2
0,5
1,2
2,5
1,2
2,5
Mains voltage
3)
[V]
305...500 +/-0 (400V Nominal voltage)
1)
Phases
3
Mains frequency
[Hz]
50 / 60 +/- 2
Output voltage
[V]
3 x 0...U Mains
Output frequency
[Hz]
see control board
Shielded motor line length
[m]
50
50
100
100
100
100
100
100
100
Storage temperature
[°C]
-25...70 °C
Operating temperature
[°C]
-10...45 °C
Model / protective system
IP20
Relative humidity
max. 95% without condensation
Tested in accordance with...
EN 61800-3
Climatic category
3K3 in accordance with EN 50178