Functional Description
Chapter
Section
Page
Date
Operating and Appliance Displays
Adr.
min
max
default
Adr.
min
max
default
Adr.
min
max
default
Adr.
min
max
default
Adr.
min
max
default
ud.11
!ud.11!
2006h
ru. 6
Setpoint frequency display
0,0125
Hz
-
409,58
-409,58
Display of the current setpoint frequency. The display occurs as in ru.3. For control reasons the setpoint frequency is
also indicated, when control release or direction of rotation are not actuated. If no direction of rotation is adjusted, the
setpoint frequency for clockwise rotation (forward) is displayed.
With ud.10 the display can be changed to a resolution of 0,1 Hz.
2007h
ru. 7
Actual load
1
%
-
200
0
Display of the actual load related to the rated current of the inverter. Only positive values are displayed, thus a
differentiation between motoric and generatoric operation is not possible.
2008h
ru. 8
Peak load
1
%
-
200
0
ru.8 allows the detection of short-time peak loads during an operating cycle. For that the highest detected value of ru.7
is stored in ru.8. The peak value memory is cleared by pressing the keys UP or DOWN or by bus by writing any chosen
value to the address of ru.8. The disconnection of the inverter also results in a clearing of the memory.
2009h
ru.9
Apparent current
0,1
A
-
unit-dependent
0
Display of actual apparent curent. The maximum values depend on the size of the inverter.
200Ah
ru.10 Active current
0,1
A
-
unit-dependent
0
Display of the torque-forming active current (stator losses already deducted). Thus the display is nearly proportional to
the supplied torque. Precondition is the input of the motor data in dr.1…dr.5. The maximum values depend on the size
of the inverter.