KEB COMBIVERT F4-C
Name: Basis
6
©
KEB Antriebstechnik, 1999
All Rights reserved
Functional Description
Chapter
Section
Page
Date
Operating and Appliance Displays
Adr.
min
max
default
Adr.
min
max
default
200Fh
ru.15 Output terminal status
1
-
-
255
0
Display of the currently set external and internal digital outputs. Whether the outputs are set by inverting or real is
irrelevant for the display. According to following table a certain decimal value is given out for each digital output. If
several outputs are set then the sum of their decimal values is displayed.
Bit -No.
Decimal value
Output
Terminal
0
1
Out 1 (transistor output)
12
1
2
Out 2 (relay RLA,RLB,RLC)
1 , 2 , 3
2
4
Out 3 (relay FLA,FLB,FLC)
21 , 22 , 23
4
16
Out A (internal output A)
none
5
32
Out B (internal output B)
none
6
64
Out C (internal output C)
none
7
128
Out D (internal output D)
none
2010h
ru.16 Internal input status
1
-
-
4095
0
Display of the currently set external and internal digital inputs. The input is considered as set when it is available as
active signal for further processing (i.e. acceptance by strobe, edge triggering or logic operation). According to following
table a certain decimal value is given out for each digital input. If several inputs are set then the sum of their decimal
values is displayed.
Bit -No.
Decimal value
Input
Terminal
0
1
ST (control release)
19
1
2
RST (reset)
20
2
4
F (rotation forward)
10
3
8
R (rotation reverse)
11
4
16
I1 (prog. input 1)
4
5
32
I2 (prog. input 2)
5
6
64
I3 (prog. input 3)
6
7
128
I4 (prog. input 4)
7
8
256
IA (internal input A)
none
9
512
IB (internal input B)
none
10
1024
IC (internal input C)
none
11
2048
ID (internal input D)
none