11.1.1 Available Hardware
11.1 Network
Components
The KEB COMBIVERT F4 can be easily integrated into different networks. For that
the inverter is fitted with an operator or interface that corresponds to the bus system.
Following hardware components are available:
-
Interface Operator
Part No..:
00.F4.010-1009
serial network in RS232 or RS485-Standard
-
Bus Operator
Part No..:
00.F4.010-7009
serial network in RS485-Standard
-
InterBus Loop-Operator
Part No..:
00.F4.010-8009
-
InterBus Host Controller Board (internal)
-
InterBus Host Controller Board (external)
-
LON-Bus-Operator
Part No..:
00.F4.010-4009
-
CAN-Bus-Operator
Part No..:
00.F4-010-5009
-
Profibus-DP-Operator
Part No.:
00.F4.010-6009
-
Optical fibre interface
Part No.:
00.F4.028-0009
-
Optical fibre operator
Part No.:
00.F4.010-A009
11.1.2 Interface- and
Bus-Operator
Integrated into the Interface Operator (00.F4.010-1009) is an isolated
RS232/RS485 interface. The RS232-interface is not applicable for the
Bus-Operator (00.F4.010-7009). The telegram structure is compatible to
protocol DIN 66019 and ANSI X3.28, sub catagory 2.5, A2, A4 and ISO
1745.
RS232/RS485
PE-Connection
PIN RS485 Signal
Significance
1
–
–
reserved
2
–
TxD
transmitter signal /RS232
3
–
RxD
receive signal /RS232
4
A'
RxD-A
receive signal A/RS485
5
B'
RxD-B
receive signal B/RS485
6
–
VP
supply voltage -Plus +5V (I
max
=10mA)
7
C/C'
DGND
data reference potential
8
A
TxD-A
transmitter signal A/RS485
9
B
TxD-B
transmitter signal B/RS485