3
KEB COMBIVERT F4-C
Name: Basis
6
30.01.98
Functional Description
PI-Controller
©
KEB Antriebstechnik, 1997
All Rights reserved
Chapter
Section
Page
Date
6.11.1 The PI-Controller
6.11 PI-Controller
Picture 6.11.1
PI-Controller
The KEB COMBIVERT is equipped with a universally programmable PI-Controller,
with it pressure, temperature or dancing position controls can be set up. Through an
optimal speed detection (see Chap. 6.10) a speed control with incremental encoder,
tacho generator or pulse encoder is realizable.
The programmable PI-Controller is the heart of the entire regulation. This is shown in
all subsequent control structures. It consists of a set/actual value comparator, that
puts the system deviation on the controller. With cn.16 and cn.17 the P- or I-component
is adjustable. The parameters cn.18 and cn.19 limit the maximum manipulated varia-
ble of the controller. With the PI-Controller fade-in time (cn.26) the controller inverse
amplification factor is defined between 0…100%. Parameter cn.25 adjusts the
frequency amplification factor in Hz/%. Through parameter cn.21 as well as the digi-
tal inputs the PI-Controller or the control fade-in can be reset.
%
Hz
cn.25
-
+
ru.30
cn.18
cn.19
Reset I
di.3...10=16
Reset PI
di.3...10=15
Reset of
fade-in
di.3...10=14
cn.26
Digital Inputs
Pi-Control
Set value
Actual value
Manipulated
Variable
KP=cn.16
KI=cn.17
cn.21 PI-Reset
conditions
PI-Controller KP (cn.16)
Defines the proportional amplification factor in the range of 0,00...250,00.
Defines the integral amplification factor in the range of 0,000...30,000.
PI-Controller KI (cn.17)
Maximum correcting range
(cn.18, cn.19)
The max. positive manipulated variable is determined with cn.18 in the range of
0...100%, the max. negative manipulated variable is determined with cn.19 in the
range of 0...-100%.
With cn.21 it is possible to regulate the reset conditions for the PI-Controller. Thus
simple speed regulations are realizable for both directions of rotation.
cn.21 Function
0
PI-Controller is not reset
1
PI-Controller = 0 (is continously reset)
2
PI-Controller is reset in case of modulation off
For speed regulations adjust the value „2“, with that the I-component of the controller
is reset at LS or nOP. The value „1“ serves mainly for start-up, to reset the controller
manually.
PI-reset conditions (cn.21)