WATERCLEAN 1600
Version 03/2008
MALFUNCTIONS AND MAINTENANCE
- 81 -
Membrane input pressure too
high
Regulation fault
Inform customer service
Incorrect handling during manual
operation
Check valve settings
Cleaning tank filling level too
low
NOTE
Is indicated before starting in
automatic operation mode -
only of significance for mainte-
nance functions
No filling level, or filling level too
low in cleaning tank
System can nevertheless be
started
Fill cleaning tank
Conductivity capacity of drink-
ing water too high
NOTE
In this case, water comes out of
the industrial water outlet; the
operator or the responsible
authority must decide if the
water can be used.
Drinking water conductivity >
2 000 µS/cm
Switch system off
Shut concentrate return line
Switch system on
Membranes defective
Change membranes if neces-
sary
Raw water conductivity too high
Look for suitable raw water
source
Renew filter bag F02
Preliminary filter F02 is full
Change F02
Renew filter bag F03
Preliminary filter F03 is full
Change F03
Fault, differential pressure, pre-
liminary filter
Differential pressure of prelimi-
nary filter > 4 bar
Change preliminary filter
Other fault signals on the dis-
play
Cut out of an automatic circuit
breaker
Check the respective circuit
breaker and if necessary, acti-
vate; if it cuts out again, inform
a qualified electrician
Fault
Cause
Remedy
Summary of Contents for WATERCLEAN 1600
Page 2: ......
Page 14: ...GENERAL Version 03 2008 WATERCLEAN 1600 8 ...
Page 28: ...DESCRIPTION Version 03 2008 WATERCLEAN 1600 22 Fig 13 Anti scalant mounting kit 1 2 ...
Page 48: ...DESCRIPTION Version 03 2008 WATERCLEAN 1600 42 ...
Page 82: ...OPERATION Version 03 2008 WATERCLEAN 1600 76 ...
Page 106: ...APPENDIX Version 03 2008 WATERCLEAN 1600 100 ...
Page 108: ......
Page 110: ......