Figure 61: Grounding Cable Connection
Related
Documentation
M7i Chassis Description on page 6
•
•
Connecting the Grounding Cable to the M7i Router on page 51
M7i DC Power Cable and Cable Lug Specifications
•
DC Power Cables on page 168
•
DC Power Lugs on page 169
DC Power Cables
To supply power to the router, connect power cables to a separate, dedicated DC power
source for each power supply and attach the cables to the field-wiring terminals on each
power supply. Most sites distribute DC power through a main conduit that leads to
frame-mounted DC power distribution panels, one of which might be located at the top
of the rack that houses the router. A pair of cables (one input and one return) connects
the field-wiring terminals to the power distribution panel.
Table 22 on page 168 summarizes the specifications for the DC power cables, which you
must supply.
Table 22: DC Power Cable Specifications
Maximum
Equal
Length
Quantity and Specification
None
Two 14-AWG (2.08 mm
2
) single-strand-count wire cables for each
power supply
Copyright © 2010, Juniper Networks, Inc.
168
M7i Multiservice Edge Router Hardware Guide