10. JMD Group Description
10.1 AMP Status Group
Pr.017
I_RMS( % Motor)
This parameter displays the actual current / motor rated current percentage of cases
。
Pr.018
I_RMS( Ampere)
This parameter displays the actual current drive
。
Pr.020
ID(Field Current, %Amp)
This parameter shows the synthesis of the field current drive。
Pr.021
IQ(Torque Current, %Amplifier)
This parameter shows the synthesis of the drive torque current.
Pr.034
ALARM Status
This parameter displays the current drive abnormal state.
【Note】on the analysis of exception code, refer to chapter 15
Pr.040
Mode Registration Information
This parameter displays the drive mode version
。
Pr.043
UP AUTO RECOVER Eanble
This parameter can be set when the UP low voltage faults, you can enable or disable startup:
UP automatic recovery
【Note】When you start the UP automatic recovery function, the drive automatically performs
an internal reset software reset, all belonging to the communication virtual I / O
Will restore the initial state.
Setting
Description
0
Disable UP AUTO RECOVER
1
Enable UP AUTO RECOVER
Pr.053
PARAMETER WRITE LEVEL
Setting
Description
0
Parameter setting, the setting values are stored to
EAROM
1
Parameter setting, the setting value is not stored into
EAROM, only written to RAM,
Reset or power off, the settings will be restored.
【Note】After the reset, the set value of this parameter will be automatically cleared to 0
。