10.2 COMM PORT Group
Pr.071
Unit Address
You can set the drive mailing address (1 to 63). If the same set of RS485 communication line,
there are two or more drive units are connected,Then each drive must be given to the
different communication address for identification purposes, or communication data will be
uncontrollable chaos.
【NOTE】
Currently only open to 19200bps, 8bits, 1stop, no parity communication format.
Pr.077
BaudRate
This parameter determines the communication port communication speed.
Setting
Description
1
BaudRate =9600
2
BaudRate =19200
3
BaudRate =38400
4
BaudRate =57600
7
BaudRate =115200
Pr.081
Error Counts
This parameter shows that when a communication failure or error, every communication
fails on plus 1。
10.3 Operation Mode Group
Pr.001
Servo Mode Select
This parameter determines the drive control mode.
【NOTE】
If you do not choose the appropriate models, in some modes, not working properly,
,
Relevant purchase pattern contained models, please refer to the following table.
Setting
Description
Include Mode
STD PRT
RC VRC
FS
FC
0
Torque/Speed
2
EGEAR(STD)/PRT(Special)
include:(switch parameter=Pr.036)
(STD)EGEAR Mode
(Special)PRT Mode
3
SP2P(Smart Point To Point)
4
BP2P(Basic Point To Point)
9
RC(Rotary Cut) / VRC(Vocano Rotary Cut)
include:(switch parameter=Pr.313)
(STD)RC Mode
(Special)VRC Mode