22
%**8 = 9);
YORK, A Johnson Controls Company
69
FLN LOC REF
Commanded by FLN to temporarily “steal” input reference
control of the drive from its normal source and place it under
FLN control. This functionality is analogous to placing the
drive in HAND mode at the panel, with the reference control
being taken by FLN instead. HAND mode at the panel has
priority over this point. Thus, this point is only effective in
temporarily taking control from the analog inputs or some
other internal control functionality.
70
DI 1 ACTUAL
Indicates the status of Digital Input 1 (1 = ON, 0 = OFF).
0118, bit 2
71
DI 2 ACTUAL
Indicates the status of Digital Input 2 (1 = ON, 0 = OFF).
0118, bit 1
72
DI 3 ACTUAL
Indicates the status of Digital Input 3 (1 = ON, 0 = OFF).
0118, bit 0
73
DI 4 ACTUAL
Indicates the status of Digital Input 4 (1 = ON, 0 = OFF).
0119, bit 2
74
DI 5 ACTUAL
Indicates the status of Digital Input 5 (1 = ON, 0 = OFF).
0119, bit 1
75
DI 6 ACTUAL
Indicates the status of Digital Input 6 (1 = ON, 0 = OFF).
0119, bit 0
76
RO 1 ACTUAL
Indicates the status of Relay Output 1 (1 = ON, 0 = OFF).
0122, bit 2
77
RO 2 ACTUAL
Indicates the status of Relay Output 2 (1 = ON, 0 = OFF).
0122, bit 1
78
RO 3 ACTUAL
Indicates the status of Relay Output 3 (1 = ON, 0 = OFF).
0122, bit 0
79
RO 4 ACTUAL
Indicates the status of Relay Output 4 (1 = ON, 0 = OFF).
0123, bit 2
80
RO 5 ACTUAL
Indicates the status of Relay Output 5 (1 = ON, 0 = OFF).
0123, bit 1
81
RO 6 ACTUAL
Indicates the status of Relay Output 6 (1 = ON, 0 = OFF).
0123, bit 0
82
AI 1 ACTUAL
Indicates the input level of Analog Input 1.
0120
83
AI 2 ACTUAL
Indicates the input level of Analog Input 2.
0121
84
AO 1 ACTUAL
Indicates the output level of Analog Output 1.
0124
85
AO 2 ACTUAL
Indicates the output level of Analog Output 2.
0125
86
OK.ALARM
Indicates the current alarm state of the drive
(1 = ALARM, 0 = OK).
87
OK.MAINT
Indicates the current maintenance state of the drive
(1 = MAINT, 0 = OK).
Maintenance triggers are configured in drive parameter
Group 29.
88
ALARM WORD1
This point is a bit-field indicating active alarms in the drive.
0308
89
ALARM WORD2
This point is a bit-field indicating active alarms in the drive.
0309
90
LAST FAULT
This point is first in the drive's fault log and indicates the most
recent fault declared.
0401
91
PREV FAULT 1
This point is second in the drive's fault log and indicates the
previous fault declared.
0412
92
PREV FAULT 2
This point is last in the drive's fault log and indicates the
oldest fault in the log.
0413
93
OK.FAULT
Indicates the current fault state of the drive
(1 = FAULT, 0 = OK).
\",3%2 ,=,2
%2 ,
=,2
%@,
Summary of Contents for York AYK550
Page 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Page 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Page 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Page 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Page 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Page 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Page 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Page 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Page 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Page 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Page 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...