2
$
YORK, A Johnson Controls Company
8104
!\!#'%F
>>q
>q
>q
Sets a percentage value that is added to the process reference.
• Applies only when at least two auxiliary (constant speed) motors are running.
• See parameter 8103
REFERENCE STEP
1.
8105
!\!#'%Q
>>q
>q
>q
Sets a percentage value that is added to the process reference.
• Applies only when at least three auxiliary (constant speed) motors are running.
• See parameter 8103
REFERENCE STEP
1.
8109
#'!'\!p
>>Z
> Z
^>#
Sets the frequency limit used to start the first auxiliary motor. The first auxiliary motor starts if:
• No auxiliary motors are running.
• AYK550 output frequency exceeds the limit:
8109 + 1 Hz.
• Output frequency stays above a relaxed limit
(8109 - 1 Hz) for at least the time: 8115
AUX MOT START D
.
After the first auxiliary motor starts:
• Output frequency decreases by the value =
(8109
START FREQ
1) - (8112
LOW FREQ
1).
• In effect, the output of the speed regulated motor drops to
compensate for the input from the auxiliary motor.
See figure, where:
• A = (8109
START FREQ
1) - (8112
LOW FREQ
1)
• B = Output frequency increase during the start delay.
• C = Diagram showing auxiliary motor’s run status as frequency
increases (1 = On).
Note! 8109
START FREQ
1 value must be between:
• 8112
LOW FREQ
1
• (2008
MAXIMUM FREQ
) -1.
8110
#'!'\!pF
>>Z
> Z
^>#
Sets the frequency limit used to start the second auxiliary motor.
• See 8109
START FREQ
1 for a complete description of the operation.
The second auxiliary motor starts if:
• One auxiliary motor is running.
• AYK550 output frequency exceeds the limit: 8110 + 1.
• Output frequency stays above the relaxed limit (8110 - 1 Hz) for at least the time: 8115
AUX MOT START D
.
8111
#'!'\!pQ
>>Z
> Z
^>#
Sets the frequency limit used to start the third auxiliary motor.
• See 8109
START FREQ
1 for a complete description of the operation.
The third auxiliary motor starts if:
• Two auxiliary motors are running.
• AYK550 output frequency exceeds the limit: 8111 + 1 Hz.
• Output frequency stays above the relaxed limit (8111 - 1 Hz) for at least the time: 8115
AUX MOT START D
.
2c_%\
23 =,2
! 7
!2,2
4,
#
t
P 8115
(P 8109)+1
P 8112
A
B
f (Hz)
f
MAX
f
MIN
1
0
t
C
P 8109
A
Summary of Contents for York AYK550
Page 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Page 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Page 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Page 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Page 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Page 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Page 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Page 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Page 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Page 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Page 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...