3
YORK, A Johnson Controls Company
$
10 =
COMM
– Assigns the fieldbus Command Word as the source for the start/stop and direction commands.
• Bits 0,1, 2 of Command Word 1 (parameter 0301) activates the start/stop and direction commands.
• See Fieldbus user’s manual for detailed instructions.
11 =
TIMER
1. – Assigns Start/Stop control to Timer 1 (Timer activated =
START
; Timer de-activated =
STOP
). See
Group 36, Timer Functions.
12…14 =
TIMER
2… 4 – Assigns Start/Stop control to Timer 2…4. See Timer Function 1 above.
1002
m'F&#
]
9
Defines external control location 2 (
EXT
2) – the configuration of start, stop and direction commands.
• See parameter 1001
EXT
1
COMMANDS
above.
1003
*!'*&
Q
9
Defines the control of motor rotation direction.
1 =
FORWARD
– Rotation is fixed in the forward direction.
2 =
REVERSE
– Rotation is fixed in the reverse direction.
3 =
REQUEST
– Rotation direction can be changed on command.
2_=#,,`#,2w
23 =,2
! 7
!2,2
4,
#
Summary of Contents for York AYK550
Page 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Page 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Page 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Page 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Page 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Page 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Page 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Page 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Page 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Page 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Page 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...