YORK, A Johnson Controls Company
$
#,2 ,?,9%* 32 , ,#3
This macro configures for applications with 2 constant speeds, active PID and PID
alternating between two setpoints using digital inputs. Set PID setpoints (internal to
the drive) using parameters 4011 (
SET
1) and 4111 (
SET
2). The digital input DI3
selects the setpoints.
%@,9 73!,,24,
%@,
%@,
9902
APPLIC MACRO
12 (
DUAL SPNTCS
)
3207
SUPERV
3
PARAM
0103 (
OUTPUT FREQ
)
1102
EXT
1/
EXT
2
SEL
2 (
DI
2)
4001
GAIN
0.7
1201
CONST SPEED SEL
11 (
DI
5, 6)
4002
INTEGRATION TIME
10.0 s
1401
RELAY OUTPUT
1
7 (
STARTED
)
4010
SETPOINT SEL
19 (
INTERNAL
)
1608
START ENABLE
1
0 (
NOT SEL
)
4011
INTERNAL SETPNT
50.0%
2108
START INHIBIT
1 (
ON
)
4027
PID
1
PARAM SET
3 (
DI
3)
2202
ACCELER TIME
1
10.0 s
4101
GAIN
0.7
2203
DECELER TIME
1
10.0 s
4102
INTEGRATION TIME
10.0 s
3105
AR OVERVOLTAGE
0 (
DISABLE
)
4110
SETPOINT SEL
19 (
INTERNAL
)
3107
AR AI
<
MIN
0 (
DISABLE
)
4111
INTERNAL SETPNT
100.0%
1
SCR
2
AI1
3
AGND
4
10V
5
AI2
6
AGND
7
AO1
8
AO2
9
AGND
10 24V
11 GND
12 DCOM1
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
m
+
mA
mA
/, 4 =
0(2)…10 V or 0(4)…20 mA
Reference voltage 10 VDC
&,,4< =+_
0(4)…20 mA
#,,`#,2_
Activate to start drive
%,`%*=,2 _
Activate to select PID
#,2 ,=,2 _
Activate to select Set2
%,3
%,3F
Relay output 1 (P 1401)
Default operation:
#,,3
=>19 connected to 21
Relay output 2 (P 1402)
Default operation:
! 7
=>22 connected to 24
Relay output 3 (P 1403)
Default operation:
\,
=>25 connected to 27
&,,= ,_
0(4)…20 mA
Not configured
Analog input circuit common
%*43;=W_
0(2)…10 V or 0(4)…20 mA
Analog output circuit common
Auxiliary voltage 24 VDC
Common for DI return signals.
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
(Fault => 25 connected to 26)
i
AI1: 0(2)
…
10 V
AI2: 0(4)
…
20 mA
&
&
Jumper Settings
+
Summary of Contents for York AYK550
Page 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Page 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Page 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Page 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Page 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Page 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Page 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Page 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Page 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Page 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Page 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...