2
%**8 = 9);
YORK, A Johnson Controls Company
,3%2 ,=,2
\",3%2 ,=,2
%2 ,
=,2
%@,
1
CTRL ADDRESS
The FLN address of the drive. It can be set by FLN and by
the panel.
5302
2
APPLICATION
The Application ID for FLN on the AYK550. This ID is
assigned by Siemens for each unique application. It
correlates directly to a particular point list approved at the
time of release. Therefore, this point list shall remain fixed
once approval is granted. Any changes to the point list shall
require a new Application ID and re-approval by Siemens.
The Application ID assigned to AYK550 is 2934.
3
FREQ OUTPUT
The output frequency applied to the motor, in Hertz.
0103
4
PCT OUTPUT
The ratio of output frequency or speed to the corresponding
maximum rating, depending on control mode.
• For scalar mode, it is the ratio of Output Frequency
(parameter 0103) to Maximum Frequency (parameter
2008).
• For speed mode, it is the ratio Speed (parameter 0102) to
Maximum Speed (2002).
None. This
ratio is
calculated
by the FLN
application.
5
SPEED
The calculated speed of the motor, in RPM.
0102
6
CURRENT
The measured output current.
0104
7
TORQUE
The calculated output torque of the motor as a percentage of
nominal torque.
0105
8
POWER
The measured output power in KW. The FLN point definition
also supports horsepower by selecting English units.
0106
DRIVE TEMP
The measured heatsink temperature, in
|
C. The FLN point
definition also supports
|
F by selecting English units.
0110
10
DRIVE KWH
The drive's cumulative power consumption in kilowatt-hours.
This value may be reset by commanding FLN point 49,
RESET KWH.
0115
11
DRIVE MWH
The drive's cumulative power consumption in megawatt
hours. This value cannot be reset.
0141
12
RUN TIME
The drive's cumulative run time in hours. This value may be
reset by commanding FLN point 48, RESET RUN TIME.
0114
13
DC BUS VOLT
The DC bus voltage level of the drive.
0107
14
OUTPUT VOLT
The AC output voltage applied to the motor.
0109
15
PRC PID FBCK
The Process PID feedback signal.
0130
16
PRC PID DEV
The deviation of the Process PID output signal from its
setpoint.
0132
17
MOTOR TEMP
The measured motor temperature as set up in Group 35.
0145
18
ROTATION CNT
The motor's cumulative revolution count, in mega-
revolutions.
0142
19
N/A
20
OVRD TIME
1 of the 5 mandatory FLN points required for compatibility
with Siemens control systems. It has no functionality in the
drive application.
None
Summary of Contents for York AYK550
Page 259: ...YORK A Johnson Controls Company G 8 Fig 1 7 8 94 4 7...
Page 260: ...G YORK A Johnson Controls Company Fig 2 7 8 8 94 7...
Page 261: ...YORK A Johnson Controls Company G 7 8 6 8 94 7 Fig 3...
Page 262: ...G YORK A Johnson Controls Company Fig 4 7 8 8 94 2 7...
Page 263: ...YORK A Johnson Controls Company G Fig 5 7 8 6 8 94 7...
Page 264: ...G YORK A Johnson Controls Company Fig 6 7 8 8 8 94 7...
Page 265: ...YORK A Johnson Controls Company G Fig 7 7 8 8 94 7...
Page 266: ...2 G YORK A Johnson Controls Company Fig 8 7 8 H 8 94 4 7...
Page 267: ...3 YORK A Johnson Controls Company G Fig 9 7 8 6 H 8 94 7...
Page 268: ...G YORK A Johnson Controls Company 7 8 8 8 94 7 Fig 10...
Page 269: ...YORK A Johnson Controls Company G Fig 11 J 8 8 94 7...