Operation
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
NetOAH
AV
29546 R/W
NetOAH
Network Override
Outdoor Air
Humidity
A BAS command to override outside
air humidity (0–100 %RH)
OprOAQ
AV
29547
R
OprOAQ
Operational
Outdoor Air
Quality
Displays the active outdoor air CO
2
(PPM)
NetOAQ
AV
29549 R/W
NetOAQ
Network Override
Outdoor Air
Quality
A BAS command to override outdoor
air CO
2
(PPM)
FanVFD
AV
29551
R
SF-O
Fan % Command
Displays the output from the control
to the supply fan VFD (%)
Fan-RT
AV
29554
R
SF-Runtime
Supply Fan
Accumulated
Runtime
Displays the supply fan runtime
(hours)
FanOffDlyCool
AV
29559 R/W
FanOffDlyCool
Fan Off Delay for
Cool
A BAS command to adjust the supply
fan runtime after cooling is turned
OFF (0–255 seconds)
FanOffDlyHeat
AV
29561 R/W
FanOffDlyHeat
Fan Off Delay for
Heat
A BAS command to adjust the supply
fan runtime after heating is turned
OFF (0–30 seconds)
DAT
AV
29564
R
DAT
DAT
Displays the active DAT (°F)
DctPrs
AV
29565
R
DA-P
Discharge Air
Static Pressure
Displays the active discharge air
static pressure (iwg)
DctPrs-Sp
AV
29566 R/W
DctPrs-Sp
Duct Pressure
Setpoint
A BAS command to adjust active
duct static pressure setpoint (iwg)
DctShutdownSp
AV
29567 R/W
DctShutdownSp
Duct Pressure
Shutdown
Setpoint
A BAS command to adjust the
duct static pressure unit shutdown
setpoint (iwg.)
#ClgStgs
AV
29576
R
#ClgStgs
Number of
Cooling Stages
Installed
Displays the number of cooling
stages installed.
MinRtCoolStg
AV
29578
R
MinRtCoolStg
Minimum Runtime
for a Cooling
Stage
Displays the minimum runtime for a
cooling stage (3–10 minutes)
Circ1ClgOATCutout
AV
29581 R/W Circ1ClgOATCutout
Circuit 1 OAT
Cooling Cutout
Circuit 1 compressors are disabled
when OAT drops below this setpoint
(...75.0°F)
Circ2ClgOATCutout
AV
29582 R/W Circ2ClgOATCutout
Circuit 2 OAT
Cooling Cutout
Circuit 2 compressors are disabled
when OAT drops below this setpoint
(...75.0°F)
Freeze-Sp
AV
29592 R/W
Freeze-Sp
Freeze Condition
Setpoint
A BAS command to disable cooling
to prevent cooling coil from freezing
(20.0–32.0°F)
ClgDATUp-SP
AV
29604 R/W
ClgDATUp-SP
Cooling DAT
Upper Setpoint
The upper setpoint for the DAT reset
schedule (41.0–80.0°F)
ClgDATLo-SP
AV
29605 R/W
ClgDATLo-SP
Cooling DAT
Lower Setpoint
The lower setpoint for the DAT reset
schedule (40.0–79.0°F)
OprClgDAT-SP
AV
29607
R
OprClgDAT-SP
Operating Cooling
DAT Setpoint
Displays the active DAT setpoint (°F)
Table 32: BACnet Points List (Continued)