5586996-JSG-A-0120 | Start-Up & Operation Guide
54
Display Code
Color
Description
41
RED
Air pressure low switch is closed when inducer is OFF.
42
RED
Air pressure high switch is closed when inducer is OFF or at low speed.
43
RED
Air pressure low switch is open when it is expected to be closed.
44
RED
Air pressure high switch is open or closed when it is expected to be closed or open.
45
RED
Fuse is open.
51
RED
Primary limit is open.
52
RED
Safety checks at start-up failed. Flame circuitry idle state is incorrect.
54
RED
ID plug failure. Reserved for future use.
55
RED
Control board failure: gas valve relays, safety relays, etc.
steady
RED
Control is not functional.
rapid
RED
ID plug failure to initialize, control is not functional.
11
YELLOW
Indicates that flame rod has low current.
21
YELLOW
Indicates that flame rod has low current.
31
YELLOW
Indicates that both flame rods measured low current.
13
YELLOW
Call for heat, prime burner is in RETRY.
23
YELLOW
Call for heat, split burner is in RETRY.
52
YELLOW
Control is in idle mode, keep alive timeout is expired.
53
YELLOW
Control is in idle mode, manual override is in OFF position.
11
GREEN
Prime burner and split burner is in OFF state.
12
GREEN
Burner state purge.
13
GREEN
Prime burner is running, burner states GAS_ON, WARMUP, RUN.
33
GREEN
Split and prime burners are running.
11
GREEN/YELLOW Prime burner is OFF, split burner is in lockout.
12
GREEN/YELLOW Burner states PURGE, split burner is in lockout.
13
GREEN/YELLOW
Prime burner is running, burner states GAS_ON, WARMUP, RUN. Split burner is in
lockout.
None
None
Board not receiving 24 volts.
Modulating Gas Heat
The following sequence refers to the modulating burner
only or burners 1A and 1B, which are arranged in a split
manifold design. Any other burners (2 or 3) are con-
trolled by the staged gas sequence referenced above.
The modulating gas controller receives a demand for
heat from the unit controller through a Modbus signal.
The controller performs a system check to ensure that
all safeties are closed, the APS is open, and the modu-
lating valve is positioned correctly.
• When the system check is satisfactory, the con-
troller enters the pre-purge cycle
• During the pre-purge cycle, the controller en-
sures the APS opens and closes at the cor-
rect settings
• When the pre-purge cycle is satisfactory, the con-
troller enters the ignition cycle
Table 25: Staged Gas Heating Faults List (Continued)
• The modulating valve and inducer enters
their light-off settings
• The DSI module and the spark ignitor energize
• The 2-stage gas valve opens, allowing gas flow
• The burners ignite and the controller receives
flame rectification from the flame sensor
• The spark ignitor remains active for the dura-
tion of the ignition cycle regardless of flame
status
• When flame rectification is not estab-
lished during the ignition cycle, the con-
troller repeats the above sequence up
to three times.
• After three failed ignition attempts, the
controller enters a 1-hour lockout