Figure 44: Verasys Dashboard
Table 31: Verasys Related Documentation
Topic
Document
Technical specifications
Smart Building Hub Catalog
Page
(LIT-1901080)
Getting up and running
quickly with the MAP
gateway
Smart Building Hub Quick
Start Guide
(Part No. 24-10737-00229)
Installing and wiring a SBH
Smart Building Hub
Installation Instructions
(Part No. 24-10737-00237)
Table 32: BACnet Points List
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
TempOccTimeout
AV
29521 R/W
TempOccTimeout
Temporary
Occupancy
Timeout
A BAS command to adjust temporary
occupancy timeout (30–480 minutes)
OprZT
AV
29522
R
OprST
Operational Zone
Temperature
Displays the active ZT (°F)
ZTAlarmOffset
AV
29524 R/W
ZTAlarmOffset
ZT Alarm Setpoint
Offset
A BAS command to adjust ZT alarm
setpoint offset (0.0–25.0°F)
ZTAlarmDelay
AV
29525 R/W
ZTAlarmDelay
ZT Alarm Time
Delay
A BAS command to adjust ZT alarm
time delay (0–120 minutes)
NetZT
AV
29526 R/W
NetZT
Network Override
ZT
A BAS command to adjust network
override ZT (0.0–100.0°F)
OprIAQ
AV
29527
R
OprIAQ
Operational IAQ
Displays the active indoor air CO
2
(PPM)
NetIAQ
AV
29530 R/W
NetIAQ
Network Override
IAQ
A BAS command to override indoor
air CO
2
(0–5,000 PPM)
OprZH
AV
29531
R
OprSH
Operational
Space Humidity
Displays the active space humidity
(%RH)
NetSH
AV
29533 R/W
NetSH
Network Override
Zone Humidity
A BAS command to override zone
humidity (0–100 %RH)
OprSSO
AV
29537
R
OprSSO
Operational Zone
Temperature
Setpoint Offset
Displays the operational zone
temperature setpoint offset (Δ°F)
NetSSO
AV
29540 R/W
NetSSO
Network Override
Space Setpoint
Offset
A BAS command to override space
setpoint offset (-5.0 to 5.0 Δ°F)
OprOAT
AV
29541
R
OprOAT
Operational OAT Displays the active OAT (°F)
NetOAT
AV
29543 R/W
NetOAT
Network Override
OAT
A BAS command to override OAT
(-50.0 to 125.0°F)
OprOAH
AV
29544
R
OprOAH
Operational
Outdoor Air
Humidity
Displays the active outside air
humidity (%RH)
OA-Enth
AV
29545
R
OA-Enth
Outdoor Air
Enthalpy
Displays the active outside air
enthalpy (BTU/lb)