Johnson Controls
5586996-JSG-A-0120 | Start-Up & Operation Guide
112
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
ERV-En
MV
29787 R/W
ERV-En
ERV Enabled
A BAS command to enable ERW
0 = NO 1 = YES
HGR-En
MV
29789 R/W
HGR-En
HGRH Enabled
For Operation
A BAS command to enable HGRH
0 = none
1 = normal
2 = alternate
HGR-S
MV
29791
R
HGR-S
HGRH Status
Displays the status of HGRH
0 = OFF/idle
1 = ON/normal command
2 = ON/alternate operation command
3 = OFF/disabled
OprSafetyCmd
MV
29798
R
OprSafetyCmd
Operating Safety
Command
Displays the status of safety
command
0 = normal
1 = pressurize
2 = depressurize
3 = purge
SafetyCmdSrc
MV
29799
R
SafetyCmdSrc
Safety Command
Source
Displays the source of safety
command input:
0 = unreliable
1 = local input
2 = network sensor
3 = high priority
Safety1
MV
29800
R
Safety1
Local Safety
Command Input 1
Displays the status of local safety
command input 1 0 = false 1 = true
NetSafety
MV
29801 R/W
NetSafety
Network Override
Safety Command
A BAS command to override safety
command 0 = false 1 = true
SS-S
MV
29802
R
SS-S
Safety Switch
Status
Displays the unit safety switch status
0=normal 1=alarm
Unit-S
MV
29803
R
Unit-S
Unit Status
Displays the unit status
0 = idle
1 = SD alarm
2 = purge command
3 = start-up wizard
ExcessOutAirFlt
MV
29809
R
Not Displayed
Locally
Not Displayed
Locally
Displays the excess outside air fault
0 = normal 1 = alarm
NotEconFlt
MV
29810
R
Not Displayed
Locally
Not Displayed
Locally
Displays the economizer not available
for suitable outside air conditions
0 = normal 1 = alarm
EconDampFlt
MV
29811
R
Not Displayed
Locally
Not Displayed
Locally
Displays the economizer damper fault
0=normal 1=alarm
EconWhen
ShouldNotFlt
MV
29812
R
Not Displayed
Locally
Not Displayed
Locally
Displays the economizer available for
unfavorable outside air conditions fault
0 = normal 1 = alarm
MornW-En
MV
29822 R/W
MornW-En
Morning Warm-
Up Enabled
A BAS command to enable morning
warm-up 0 = NO 1 = YES
TempOCC
MV
29825 R/W
TempOCC
Temporary
Occupancy Input
A BAS command to enable
temporary occupancy input
0 = disable 1 = enable
Table 32: BACnet Points List (Continued)