Operation
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
EVAP-T
AV
29833
R
C1-
EvapTempValue
Evaporating
Temperature
Value Circuit 1
Displays the active temperature of
the air leaving the evaporator (°F)
LoadShedAdjust
AV
29885 R/W
LoadShedAdjust
Load Shed Adjust
A BAS command to adjust load shed
for automatic demand response (0–8
Δ°F)
Altitude
AV
29889 R/W
Altitude
Altitude
A BAS command to adjust the
altitude (-1,500 to 30,000 feet)
MornCRAT-Sp
AV
29892 R/W
MornCRAT-Sp
Morning Cool
Down/RAT
Setpoint
A BAS command to adjust morning
cool down/RAT setpoint (50–85°F)
EarlyStrtPeriod
AV
29895 R/W
EarlyStrtPeriod
Early Start Period
A BAS command to adjust early start
period (0–120 minutes)
DeviceId
AV
29897 R/W
DeviceId
Device OID
A BAS command to input device
object ID (0–4194302)
UnoccDehumSP
AV
29903 R/W
HGRUnoccHum-
SP
HGRH UNOCC
Humidity Setpoint
A BAS command to adjust HGRH
UNOCC humidity setpoint (0-100%)
SZVAVMinFanSpd
AV
29913 R/W
SZVAVMinFanSpd
SZVAV Minimum
Fan Speed
A BAS command to adjust the SZVAV
minimum fan speed (20–67%)
EconAlrmDly
AV
29916 R/W
EconAlrmDly
FDD Economizer
Alarm Delay
A BAS command to adjust
economizer FDD alarm delay
(1–3,600 seconds)
EconPosErr
AV
29917 R/W
EconPosErr
FDD Economizer
Damper Allowed
Error
A BAS command to adjust the outside
air damper feedback versus actual
position error tolerance (0–100%)
EconMinErr
AV
29918 R/W
EconMinErr
FDD Damper
Min Position
Tolerance
A BAS command to adjust the outside
air damper feedback versus actual
position tolerance in error (0–10%)
StgClgCmd
AV
29922
R
StgClgCmd
Staged Cooling
Command
Displays the cooling command (%)
StgHtgCmd
AV
29923
R
StgHtgCmd
Staged Heating
Command
Displays the heating command (%)
PropHtgCmd
AV
29924
R
PropHtgCmd
Proportional
Heating
Command
Displays the proportional heating
command for all modulating heat
options (%)
C1A-Starts
AV
29941
R
C1A-Starts
Compressor
Number Times
ON 1A
Displays the compressor 1A start
count
C1B-Starts
AV
29942
R
C1B-Starts
Compressor
Number Times
ON 1B
Displays the compressor 1B start
count
C2A-Starts
AV
29944
R
C2A-Starts
Compressor
Number Times
ON 2A
Displays the compressor 2A start
count
C2B-ASCDTmr
AV
29945
R
C2B-ASCDTmr
Anti-Short Cycle
Delay Time
Remaining 2B
Displays the time remaining for
compressor 2B to turn ON (seconds)
C2BOnTimer
AV
29947
R
C2BOnTimer
Min. ON Time
Remaining 2B
Displays the minimum time remaining
for compressor 2B to turn OFF
(seconds)
Table 32: BACnet Points List (Continued)