Start-Up & Operation Guide | 5586996-JSG-A-0120
65
Operation
Table 26: Menus and Submenus (Continued)
Menu
Submenu
Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Status
(
SmokeCtrl
Safety2 (Local Safety Command Input 2)
/ False
False, True
Safety3 (Local Safety Command Input 3)
/ False
False, True
NetSafety (Network Override Safety
Command) / False
False, True
SMOKE-A (Smoke Detector) / Normal
Normal, Alarm
Status
Unit-S (Unit Status) / Idle
Idle, SD Alarm, Purge Command, Start-Up
Wizard, Morning Warm-Up, Air Tempering,
Dehumidification, Heating, Cooling, Economizer,
Fan Only, Comfort Ventilation, Start-Up Delay,
Disabled, Updating Software
Econ-S (Economizer Status)
Disabled, Damper Not Functional, Purge,
Unavailable-Sensor Fault, Economizer Loading,
SAT High Limit, Mixed Air Low Limit Cycle,
Demand Ventilation Air Quality, Outdoor Airflow
Control, Free Cooling is Active, Minimum Position,
Test, Comfort Ventilation, Low Outside Air Ambient
ExRt-S (Exhaust Return Fan Status)
OFF-Idle, ON-Normal Command, OFF-Disabled,
OFF-VFD Fault, OFF-Low Building Static Pressure,
OFF-Economizer Damper Position
SupplyF-S (Supply Fan Status) / OFF-
Idle
OFF-Idle, ON-Purge, ON-Gas Valve or Limit Fault,
ON, ON-Thermostat Request, ON-Fan Off Delay
for Cool, ON-Fan Off Delay for Heat,
ON-Continuous Fan Occupied Operation, ON-
Normal Command, OFF-Exceeding Duct Pressure
Shutdown SP, OFF-Low Voltage, OFF-Fan
Overload Lockout, OFF-Fan VFD Fault, OFF-Hot
Water Freeze Stat, OFF-Air Proving Switch, OFF-
Minimum Off Delay, OFF-Fan On Delay For Heat,
OFF-Fan Off Delay for Cool
HGR-S (Hot Gas Reheat Status) / OFF-
Idle
OFF-Idle, On-Normal Command, On-Alternate
Operation Command, OFF-Disabled
Clg-S (Cooling Status) / OFF-Idle
OFF-Idle, Thermostat Cooling, Unoccupied
Cooling, Occupied Cooling, OFF-OAT Lockout,
OFF-Disabled, OFF-Lockout, OFF-Low Supply
Voltage, OFF-Low Ambient, OFF-Low Ambient Pre-
Run Delay, OFF-Waiting For Changeover Delay,
OFF-Free Cooling, Comfort Ventilation
Htg-S (Heating Status) / OFF-Idle
OFF-Idle, ON, SAT Tempering, Morning Warmup,
Thermostat Heating, Unoccupied Heating,
Occupied Heating, OFF-Disabled, OFF-OAT
Lockout, OFF-SAT Limit, OFF-Waiting for
Changeover Delay, Comfort Ventilation
PFILT-DP (Pre-Filter Differential
Pressure)
iwg
FFILT-DP (Final Filter Differential
Pressure)
iwg
PHASE-A (Phase Monitor Alarm) / Normal Normal, Alarm
24VAC (24VAC Input) / Displays Active
Voltage
Volts (V)