Johnson Controls
5586996-JSG-A-0120 | Start-Up & Operation Guide
100
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
ClgOcc-Sp
AV
29608 R/W
ClgOcc-Sp
OCC Cooling
Setpoint
The occupied cooling setpoint
(45.0–98.0°F)
ClgUnocc-Sp
AV
29609 R/W
ClgUnocc-Sp
UNOCC Cooling
Setpoint
The unoccupied cooling setpoint
(46.0–99.0°F)
OprClg-Sp
AV
29610
R
OprClg-Sp
Operating Cooling
Setpoint
Displays the active operating cooling
setpoint (0.0–100.0°F)
C1A-RunTime
AV
29627
R
C1A-RunTime
Compressor
Accumulated
Runtime 1A
Displays the operating hours of
compressor 1A (hours)
C1B-RunTime
AV
29628
R
C1B-RunTime
Compressor
Accumulated
Runtime 1B
Displays the operating hours of
compressor 1B (hours)
C2A-RunTime
AV
29630
R
C2A-RunTime
Compressor
Accumulated
Runtime 2A
Displays the operating hours of
compressor 2A (hours)
C1AOnTimer
AV
29631
R
C1AOnTimer
Min. ON Time
Remaining 1A
Displays the minimum time
remaining for compressor 1A to turn
off (seconds)
C1BOnTimer
AV
29632
R
C1BOnTimer
Min. ON Time
Remaining 1B
Displays the minimum time
remaining for compressor 1B to turn
off (seconds)
C2AOnTimer
AV
29634
R
C2AOnTimer
Min. ON Time
Remaining 2A
Displays the minimum time
remaining for compressor 2A to turn
off (seconds)
C1A-ASCDTmr
AV
29635
R
C1A-ASCDTmr
Anti-Short Cycle
Delay Time
Remaining 1A
Displays the time remaining for
compressor 1A to turn on (seconds)
C1B-ASCDTmr
AV
29636
R
C1B-ASCDTmr
Anti-Short Cycle
Delay Time
Remaining 1B
Displays the time remaining for
compressor 1B to turn on (seconds)
C2A-ASCDTmr
AV
29638
R
C2A-ASCDTmr
Anti-Short Cycle
Delay Time
Remaining 2A
Displays the time remaining for
compressor 2A to turn on (seconds)
SLP-1
AV
29671
R
SLP-1
Suction Line
Pressure 1
Displays the active system 1 suction
line pressure (psi)
SLP-2
AV
29672
R
SLP-2
Suction Line
Pressure 2
Displays the active system 2 suction
line pressure (psi)
LLP-1
AV
29675
R
LLP-1
Liquid Line
Pressure 1
Displays the active system 1 liquid
line pressure (psi)
LLP-2
AV
29676
R
LLP-2
Liquid Line
Pressure 2
Displays the active system 2 liquid
line pressure (psi)
SLT-1
AV
29679
R
SLT-1
Suction Line
Temperature 1
Displays the active system 1 suction
line temperature (°F)
SLT-2
AV
29680
R
SLT-2
Suction Line
Temperature 2
Displays the active system 2 suction
line temperature (°F)
LLT-1
AV
29683
R
LLT-1
Liquid Line
Temperature 1
Displays the active system 1 liquid
line temperature (°F)
LLT-2
AV
29684
R
LLT-2
Liquid Line
Temperature 2
Displays the active system 2 liquid
line temperature (°F)
Table 32: BACnet Points List (Continued)