Johnson Controls
5586996-JSG-A-0120 | Start-Up & Operation Guide
116
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
Humidistat
MV
30063
R
Humidistat
Humidistat
A BAS command that allows the
control of unit by humidistat
0 = OFF 1 = ON
HtgOcc-En
MV
29722 R/W
HtgOcc-En
MZVAV Occupied
Heating Enabled
A BAS command that allows the user
to enable MZVAV occupied heating
mode
0 = NO 1 = YES
HtgClgSP-Mode
MV
30064 R/W
HtgClgSP-Mode
Heat Cool
Setpoint Mode
A BAS command that allows the user
to enable heat cool setpoint mode
0 = NO 1 = YES
Common-SP
AV
30065 R/W
Common-SP
Common Setpoint
A BAS command to adjust common
setpoint (45.0–98.0°F)
OprEvapTempSp
AV
30066
R
OprEvapTempSp
Operational Evap
Temperature
Setpoint
Displays the active evaporator
temperature setpoint (°F)
OprHGRTempSp
AV
30067
R
OprHGRTempSp
Operational
HGRH
Temperature
Setpoint
Displays the active HGRH
temperature setpoint (°F)
DemLoadshd
MV
30075
R
DemLoadshd
Demand
Loadshed
Displays the demand load shed
command status 0 = NO 1 = YES
SafetySetupNI
MV
30079 R/W
SafetySetupNI
Safety Setup
Network Input
A BAS command to enable safety
setup
0 = Normal
1 = Pressurize
2 = Depressurize
3 = Purge
4 = Shutdown
MVCritical
ActiveEvent
0
30000
R
NA
NA
NA
MVCritical
InactiveEvent
0
29999
R
NA
NA
NA
MVServicePriority
ActiveEvent
0
29998
R
NA
NA
NA
MVServicePriority
InactiveEvent
0
29997
R
NA
NA
NA
MVService
ActiveEvent
0
29996
R
NA
NA
NA
MVService
InactiveEvent
0
29995
R
NA
NA
NA
NOTE:
NA = Not Available
Table 32: BACnet Points List (Continued)