Johnson Controls
Start-Up & Operation Guide | 5586996-JSG-A-0120
115
Operation
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
H8
MV
29992
R
H8
Heating Stage
Command 8
Displays the command of heating
stage 8 0 = OFF 1 = ON
H8-S
MV
29994
R
H8-S
Heating Stage 8
Status
Displays the status of heating stage 8
0 = OFF/idle
1 = ON/minimum runtime timer
2 = ON/normal command
3 = OFF/heating is disabled
HGRB-C
MV
30005
R
HGRB-C
HGRH Bleed
Valve Command
Displays the command of HGRH
bleed valve 0 = OFF 1 = ON
HRW-C
MV
30007
R
HRW-C
Heat Recovery
Wheel Command
Displays the command of ERW
0 = OFF 1 = ON
HRW-S
MV
30009
R
HRW-S
Heat Recovery
Wheel Status
Displays the status of ERW
0 = OFF
1 = max cooling
2 = max heating
3 = blocking protection"
Hum-En
MV
30013 R/W
Hum-En
Humidification
Enabled
A BAS command to enable
humidification
0 = disable 1 = enable
LowCoolCapAlm
MV
30015
R
LowCoolCapAlm
Insufficient
Cooling Capability
Alarm
Displays alarm for active temperature
below setpoint in cooling mode
0 = normal 1 = alarm
LowHeatCapAlm
MV
30016
R
LowHeatCapAlm
Insufficient
Heating Capability
Alarm
Displays alarm for active temperature
below setpoint in heating mode
0 = normal 1 = alarm
Safety2
MV
30023
R
Safety2
Local Safety
Command Input 2
Displays the status of local safety
command input 2 0 = false 1 = true
Safety3
MV
30024
R
Safety3
Local Safety
Command Input 3
Displays the status of local safety
command input 3 0 = false 1 = true
RunContAlm
MV
30027
R
RunContAlm
Unit Running
Continuously
Alarm
Displays the status of unit running
continuously alarm
0 = normal 1 = alarm
SFVFD2Flt
MV
30031
R
SFVFD2Flt
Supply Fan VFD
2 Fault
Displays the status of the supply fan
VFD2 fault 0 = normal 1 = alarm
SMOKE-A
MV
30032
R
SMOKE-A
Smoke Detector
Displays the smoke alarm fault
0 = normal 1 = alarm
SPNoChangeAlm
MV
30033
R
SPNoChangeAlm
Setpoint Not
Changing Alarm
Displays the status of unit setpoint
not changing alarm
0 = normal 1 = alarm
UVLight-En
MV
30036 R/W
UVLight-En
UV Light Installed
A BAS command that allows UV light
to be enabled 0 = NO 1 = YES
UVLight-Reset
MV
30037 R/W
UVLight-Reset
UV Light Runtime
Reset
A BAS command that allows UV light
runtime to be reset
0 = OFF 1 = reset
UVLight-Service
MV
30039
R
UVLight-Service
UV Light Needs
Service
Displays the UV light service alarm
0 = normal 1 = alarm
Condensate
Alarm
MV
30062
R
COND-A
Condensate
Alarm
Displays the condensate alarm fault
Table 32: BACnet Points List (Continued)