Johnson Controls
Start-Up & Operation Guide | 5586996-JSG-A-0120
33
Operation
Table 16: Building System Interface Board Field Terminal Points
Callout
Name
Description
IO Type
IO Number
Pin
1
EAD-REF
Exhaust Air Damper Reference
AI
13
W8
2
EF-REF
Exhaust Fan Speed Reference
AI
14
W37
3
OAD-REF
Outdoor Air Damper Reference
AI
15
W6
4
ZN-H
Zone Humidity
AI
17
W4
5
ZN-T
Zone Temperature
AI
18
W45
6
HTGV-O
Heating Valve Output
AO
1
W32
7
HUM-O
Humidifier Output
AO
2
W30
8
ADR-S
Demand Shed Input
BI
1
W28
9
ISOD1-S
Isolation Damper 1 Status
BI
2
W27
10
ISOD2-S
Isolation Damper 2 Status
BI
3
W25
11
SMOKE1-S
Smoke Sequence 1 Status
BI
4
W24
12
SMOKE2-S
Smoke Sequence 2 Status
BI
5
W22
13
SMOKE3-S
Smoke Sequence 3 Status
BI
6
W21
14
G-FAN
G Fan Thermostat Input
BI
7
W53
15
Y1-LOWCOOL
Y1 Low Cool Thermostat Input
BI
8
W55
16
Y2-HIGHCOOL
Y2 High Cool Thermostat Input
BI
9
W52
17
W1-LOWHEAT
W1 Low Heat Thermostat Input
BI
10
W51
18
W2-HIGHHEAT
W2 High Heat Thermostat Input
BI
11
W50
19
HUMIDISTAT
Humidistat Input
BI
12
W49
20
ALARM1-C
Alarm 1 Command
BO
6
W17
21
ALARM2-C
Alarm 2 Command
BO
7
W16
22
HUM-C
Humidifier Command
BO
8
W14
23
ISOD-C
Isolation Damper Command
BO
9
W13
24
VAVHTG-C
MZVAV Heat Command
BO
10
W60
8
9 10 11 12 13 14 15 16 17 18 19
6 7
1 2 3
4 5
20 21 22 23
24
LD27997
Figure 8: Building System Interface Board