5586996-JSG-A-0120 | Start-Up & Operation Guide
72
Table 26: Menus and Submenus (Continued)
Menu
Submenu
Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Commission
(
Commissioning
Mode > Cooling
HGRB-C (Hot Gas Reheat Bleed Valve
Command)
Close, Open
Commissioning
Mode > Heating
Commissioning Mode / Disable
Disable, Enable
Commissioning Time Remaining
minutes
Extend Commissioning Time
No, Yes
SF-C (Supply Fan Command)
OFF, ON
SF-O (Fan % Command)
% (0–100)
H1 (Heating Stage Command 1)
OFF, ON
ModHtgOut (Modulating Heat Output)
% (0–100)
H2 (Heating Stage Command 2)
OFF, ON
H3 (Heating Stage Command 3)
OFF, ON
H4 (Heating Stage Command 4)
OFF, ON
H5 (Heating Stage Command 5)
OFF, ON
H6 (Heating Stage Command 6)
OFF, ON
H7 (Heating Stage Command 7)
OFF, ON
H8 (Heating Stage Command 8)
OFF, ON
HWV (Hydronic Heat Valve %
Command) / 0%
% (0–100)
VAV Box (MZVAV Box Heat Command) /
OFF
OFF, ON
Network Setup
FcBusMode (On units with a BACnet IP
card installed, BACnet MS/TP, Modbus,
and N2 are not functional. Select one of
the available parameters.)
Wired Field Bus, Wireless Field Bus, N2 Field
Bus, Modbus Field Bus, Ethernet Field Bus,
Indeterminate FC Bus Mode
Address
BACnet Integration Setup on page 94
DeviceId
BaudRate
Auto, 1200, 9600, 19200, 38400, 76800
DevName
Premier RTU (Default)
EncodeType / ANSI X3.4 (US-ASCII)
ISO 10646 (UCS-2), ANSI X3.4 (US-ASCII),
Microsoft
®
DBCS code page 932 (Japanese Shift
JIS), ISO 10646 (UTF-8)
IP Address
BACnet Integration Setup on page 94
IP Mask
IPRouterAddress
StaticIPAddress
StaticIPMask
StaticIPRouterAdrs
ApplyStaticIP
DHCP-En
Twinning
Group ID, Default - 0
(0–100)
Device# (Device Number) / 0
(0–100)
Offline
No, Yes
OnlineDevCount (Online Device Count)
counts
IsoDmpr
Close, Open