Operation
Table 26: Menus and Submenus (Continued)
Menu
Submenu
Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Commission
(
Air Balance >
Supply
MaxAirflow
cfm (0–100,000)
Econ (Economizer Damper %
Command)
%
OAPctOvr-Mode (Economizer Damper
Percent Override Mode) / OFF
OFF, ON
OAPctOvr-Pos (Economizer Damper
Percent Override Position) / 0%
% (0-100)
SF-O (Fan % Command)
0%
SFPctOvr-Mode (Supply Fan Percent
Override Mode) / OFF
OFF, ON
SFPctOvr-Pos (Supply Fan Percent
Override Position) / 0%
% (0-100)
Fr Air (Fresh Air Intake Value)
cfm
MOAFlow-Sp (Fresh Air Intake Setpoint)
cfm (0-50,000)
MOA-Range (Fresh Air Intake Max
Sensor Range)
cfm (0-750,000)
DA-P (Discharge Air Static Pressure)
iwg
DctPrs-Sp (Duct Pressure Setpoint) / 1.5 iwg (0-5)
BldgPres (Building Static Pressure)
iwg
Bldg-Sp (Building Pressure Setpoint)
iwg (-0.25 to 0.25)
Supply Flow Value
cfm
Supply Pickup Gain
0–100
Supply Area
square feet (0–100)
Altitude
feet (-1,500 to 30,000)
SZVAVClgMinFan (SZVAV Cooling
Minimum Fan Speed)
% (20–67)
SZVAVHtgMinFan (SZVAV Heating
Minimum Fan Speed)
% (20–67)
SZVAVMinFanSpd (SZVAV Minimum
Fan Speed)
% (20–67)
HighSpeedFan-MinPos (Economizer
Damper Minimum Position High Speed
Fan) / 5%
% (0–100)
LowSpeedFan-MinPos (Economizer
Damper Minimum Position Low Speed
Fan) / 25%
% (0–100)
SF-LowSpd-SP (Supply Fan Low Speed
Threshold) / 50%
% (0–100)
DVentMaxEconPos (Demand Ventilation
Maximum Economizer Position) / 50%
% (0–100)
MaxOAFlow (Maximum Outside Airflow)
cfm (0–100,000)
Air Balance >
Return
Air Balance Mode / Disable
Disable, Enable
Export Air Balancing Report
UnitEn (Unit Enable) / Enable
Shutdown, Enable
RAD-O (Return Air Damper Command)
%
RFPctOvr-Mode (Return Fan Percent
Override Mode)
OFF, ON