SECTION 2 – INSTALLATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
2
75 - 105 TON MODELS
MODEL SIZE
075
080
090
105
Filters -12” Rigid 65%, 2” 30% Prefilter (Pre-Filter Position)
Quantity
2 / 8 / 9
2 / 8 / 9
8 / 12
8 / 12
Size (length x width) (in.)
16x20/25x16/25x20 16x20/25x16/25x20
25x16/25x20
25x16/25x20
Total Filter Face Area (square feet)
55.8
55.8
61.6
61.6
Filters -12” Rigid 95%, 2” 30% Prefilter (Pre-Filter Position)
Quantity
2 / 8 / 9
2 / 8 / 9
8 / 12
8 / 12
Size (length x width) (in.)
16x20/25x16/25x20 16x20/25x16/25x20
25x16/25x20
25x16/25x20
Total Filter Face Area (square feet)
55.8
55.8
61.6
61.6
Filters - 2” Carbon (Pre-Filter Position)
Quantity
10 / 15
10 / 15
12 / 18
12 / 18
Size (length x width) (in.)
25x16 / 25x20
25x16 / 25x20
25x16 / 25x20
25x16 / 25x20
Total Filter Face Area (square feet)
77.1
77.1
92.5
92.5
Filters - 12” Rigid 95% In Post-Filter Position
Quantity
10 / 15
10 / 15
12 / 18
12 / 18
Size (length x width) (in.)
25x16 / 25x20
25x16 / 25x20
25x16 / 25x20
25x16 / 25x20
Total Filter Face Area (square feet)
77.1
77.1
92.5
92.5
Gas Furnace
Staged Furnace Sizes
(input/output/stages)
375 mbh / 300 mbh / 2 stages
750 mbh / 600 mbh / 4 stages
1125 mbh / 900 mbh / 6 stages
Inlet Gas Pressure
Range (min. to max. iwg)
Natural
4.5–10.5 iwg
Propane
11.0–13.0 iwg
Minimum Air ON Temperature
6,950–36,000
11,150–36,000
15,150–36,000
15,150–36,000
Airflow Range (min. to max. cfm)
375 mbh / 300 mbh / 8:1 turndown
Modulating Furnace Sizes
(input/output/turndown)
750 mbh / 600 mbh / 16:1 turndown
1125 mbh / 900 mbh / 24:1 turndown
4.5–10.5 iwg
Inlet Gas Pressure
Range (min. to max. iwg)
Natural
11.0–13.0 iwg
Propane
8,250–36,000
11,150–36,000
15,150–36,000
15,150–36,000
Minimum Heat Exchanger Entering Supply
Air Temperature
40 °F
Electric Heaters
Size Range (min. to max. kW)
80–200
108–250
108–250
108–250
Heating steps
1
2–6
2–6
2–6
2-6
Minimum Outside Air Temp. for Mech.
Cig.
45
45
45
45
Low Ambient Option Min. Outside Air
Temp
0
0
0
0
1.
Electric heat steps and airflow range depends on voltage and size. Consult the air pressure drop tables for specific number of steps for a
given voltage.
2. Weights are for components only and need to be added to the extended cabinet weights. The diffuser is required in the extended cabinet
for any unit with hot water or final filter option.
TABLE 3 -
PHYSICAL DATA (CONT'D)