SECTION 6 – USER INTERFACE CONTROL CENTER
TABLE 45 -
SUPPLY SYSTEM
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SETTING
LOCATION
SHOW WHEN UNIT TYPE IS
SUPPLY SYS STATUS
Normal - Active
Normal - Inactive
Safety Trip Safety
Fault Safety
Lockout
Always
SUPPLY FAN
OUTPUT
On - Off
Derived
Always
STATUS
Running Stopped
Derived
SUPPLY FAN VFD
SPEED
0–100%
Derived
Unit Type Equals Variable Air
Volum Or FLEXSYS
SINGLE ZONE VAV
MIN VFD SPEED
33–66%
50%
Unit Type equals Single Zone
VAV
DUCT STATIC PRESS
CURRENT
0.00–5.00 iwg
Look Up Table
Unit Type Equals Variable Air
Volum Or FLEXSYS
ACTIVE SP
0.00 To 5.00 iwg
Derived
RETURN FAN
OUTPUT
On - Off
Derived
Power Exhaust Type Equals
Return W/E Return W/O
Exhaust Fans
STATUS
Running Stopped
Derived
EXHAUST / RETURN
FAN VFD
0–100%
Derived
Power Exhaust Type Equals
Return W/E Return W/O
Exhaust Fans
RETURN FAN PRESS
CURRENT
-1.00 To +1.00 iwg
Look Up Table
Power Exhaust Type Equals
Return W/E Return W/O
Exhaust Fans
ACTIVE SP
0.00–1.00 iwg
Derived
DUCT PRESS
TRANSDUCER
SPAN
2
1.25, 2.5, 5.0
5.0
Setpoints /
Supply System
Unit Type Equals Variable Air
Volum Or FLEXSYS
DUCT STATIC
RESET LOW SETP
1
0–1 iwg - Span 0
iwg To Duct Static
Reset High
1.5 In-Wg
Setpoints /
Supply System
Unit Type Equals Variable Air
Volum Or FLEXSYS
DUCT STATIC
RESET HIGH SETP
1
Duct Static Reset
Low Limit To Span
2.5 In-Wg
Setpoints /
Supply System
Unit Type Equals Variable Air
Volum Or FLEXSYS
DUCT STATIC OVER
PRESSURE
2
0 - I iwg - 5 In-Wg
3.0 In-Wg
Setpoints /
Supply System
Unit Type Equals Variable Air
Volum Or FLEXSYS
RETURN
PRESSURE HIGH
SETP
2
0.15–0.45
0.15
Setpoints /
Supply System
Power Exhaust Equals Return
W/Exhaust