SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
7
MORNING WARM UP
This parameter is programmed through the PROGRAM key. This tells the IPU board if the
Morning Warmup option is available or not. When it is programmed to USER ENABLED,
Morning Warm Up is available to be used. When it is programmed to USER DISABLED,
Morning Warm Up is unavailable.
MORNING WARM UP
MAX TIME
This parameter is programmed through the SETPOINTS key. This value is the maximum time
the IPU board will allow for Morning Warm Up when the unit is in the Adaptive Morning Warm
Up mode. If the derived Morning Warm Up Opt Time exceed this time the Morning Warm Up
Max Time is used.
MORNING WARM UP
OPT TIME
This is the average of the previous three days Warm Up times plus 10 minutes. This value
is used to determine the Morning Warm Up start time for the next day when the unit is in the
Adaptive Morning Warm Up mode.
NIGHT SET BACK
This parameter is programmed through the PROGRAM key. This parameter allows the user to
enable or disable Night Set Back. If this parameter is disabled Unoccupied Heating will not be
available. The two parameters to choose from are USER ENABLED or USER DISABLED.
OA DAMPER MAXIMUM
POSITION
This parameter is programmed through the SETPOINTS key. This establishes the maximum
amount of ventilation air to be used in a Demand Ventilation situation.
OA DAMPER MINIMUM
POSITION
This parameter is programmed through the SETPOINTS key. This establishes the minimum
amount of ventilation air to be used when the unit is in the Occupied mode.
OA DAMPER POSITION
ACTIVE SP
This is the damper position setpoint, in percent open, the IPU board is trying to maintain.
OA DAMPER POSITION
CURRENT
This is the actual output, in percent open to the outdoor air damper.
OUTSIDE AIR ENTHALPY
This indicates the total heat content of the outdoor air.
OUTSIDE AIR HUMIDITY
This is the outdoor air relative humidity.
OUTSIDE AIR TEMP
This is the outdoor air dry bulb temperature.
OAT SETPOINT FOR
HIGH SAT
This parameter is programmed through the SETPOINTS key. When the outdoor temperature is
equal to or less than this temperature the Active Supply Air Temperature Setpoint on a Variable
Air Volume Unit is set to the SAT HIGH SETPOINT.
OAT SETPOINT FOR
LOW SAT
This parameter is programmed through the SETPOINTS key. When the outdoor temperature
is equal to or greater than this temperature the Active Supply Air Temperature Setpoint on a
Variable Air Volume Unit is set to the SAT LOW SETPOINT.
OUTSIDE AIR ENTHALPY
SETPOINT
This parameter is programmed through the SETPOINTS key and is the upper limit of outdoor
enthalpy that can be used for economizer operation. If the outdoor air enthalpy is above this
value, the economizer is made inactive.
OUTSIDE AIR FLOW
ACTIVE SP
This is the airflow setpoint that the IPU board is trying to maintain.
OUTSIDE AIR MAXIMUM
FLOW
This parameter is programmed through the SETPOINTS key. When air measurement stations
are installed and the unit is in the Demand Ventilation mode, this is the maximum allowable
airflow value.
OUTSIDE AIR MINIMUM
FLOW
This parameter is programmed through the SETPOINTS key. When air measurement stations
are installed and the unit is in the Demand Ventilation mode, this is the minimum airflow value.
POWER EXHAUST TYPE
This parameter is programmed through the OPTIONS key and tells the IPU board what type
of Exhaust is installed. The choices are None, On-Off Damper Cntrl, On-Off Press Cntrl,
Modulate Damper VFD, Return Fan W/Exh, or Return Fan W/O Exh.
PRESS TRANS PKG
This parameter is programmed through the OPTIONS key. This identifies to the IPU board
which of the compressor systems are configured with suction and discharge pressure
transducers. The options are None, Sys 1; Sys 1, 2; or Sys 1, 2 and 3.
PRESSURE
DISCHARGE*
This is the discharge pressure and is shown for each compressor system if pressure
transducers are installed and configured for the system.
PRESSURE SUCTION*
This is the suction pressure and is shown for each compressor system if pressure transducers
are installed and configured for the system.
TABLE 54 –
DEFINITIONS (CONT'D)