JOHNSON CONTROLS
154
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
SECTION 6 – USER INTERFACE CONTROL CENTER
BACNET
NAME
USER INTERFACE
NAME
READ/
WRITE
BACNET
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
TEMP_2_SUCT
Suct Temp Ckt 2
R
AI51
564
Displays The Actual System 2 Suct Line
Temp (°F)
TEMP_2_
SUPER
Suct Superheat
Ckt 2
R
AI52
565
Displays The System 2 Superheat (°F)
TEMP_3_SUCT
Suct Temp Ckt 3
(70-150 Ton Only)
R
AI53
566
Displays The Actual System 3 Suct Line
Temp (°F)
TEMP_3_
SUPER
Suct Superheat Ckt
3 (70-150 Ton Only)
R
AI54
567
Displays The System 3 Superheat (°F)
UND_FLR_
DEWP
Underfloor Slab
Dew Point (FlexSys)
R
AI55
568
Displays The Calculated Dew Point Of The
Underfloor Air (
°F)
UND_FLR_
HUMD
Underfloor Air
Humidity (FlexSys)
R
AI56
569
Displays The Humidity Value Of The
Underfloor Air Thast The Unit Is Controlled
To (°F)
UND_FLR_
TEMP
Undefloor Slab
Temp (FlexSys)
R
AI57
570
Displays The Temp Of The Underfloor Air
That The Unit Is Contolling To (°F)
UND_HUMD_
BAS
Underfloor Air
Humidity BAS
R/W
AV36
1061
Allows The BAS System To Input An
Underfloor Air Humidity Value To The
Control. (%) "Under Flr Humi BAS" Must
Be Enabled In The Service Menu For This
Point To Function
UND_TEMP_
BAS
Underfloor Slab
Temp BAS
R/W
AV37
1062
Allows The BAS System To Input An
Underfloor Air Temp Value To The Control
(°F) "Under Flr Temp BAS" Must Be
Enabled In The Service Menu For This
Point To Function
UNIT_MODE
Current Oper Mode
R
AI58
571
Displays The Current Operating Mode:
0=OCC Cool
1=OCC Cool Low
2=OCC Cool High
3=OCC Cool W/ Byp
4=OCC Cool W/O Byp
5= OCC Heat
6=OCC Heat Low
7=OCC Heat High
8=OCC Standby
9=UNOCC Cool
10=UNOCC Cool Low
11=UNOCC Cool High
12=UNOCC Heat
13=UNOCC Heat Low
14=UNOCC Heat High
15=UNOCC Standby
16=Comfort Vent Cool
17=Comfort Vent Heat
18=Night Set-Back
19=Morning Warm-Up
20=Power Up Standby
TABLE 53 –
BACNET MS/TP, MODBUS, BACNET IP (SEE NOTES AT END OF TABLE) (CONT'D)