SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
6
SETPOINTS
All SETPOINTS values are numeric. Setpoints param-
eters can be viewed under their respective menu select
key on the left side of the keypad. However, they can
only be changed under the SETPOINTS key using the
following procedure.
Press the SETPOINTS key to enter the menu. The
Enter Password screen appears. All setpoints param-
eters require the use of a password before they can be
changed. See the
for
information on how to enter a password into the UI.
When a Level 1 password is entered, only Level 1 set-
points are available to change. Entering a Level 2 pass-
word makes all setpoints available.
After the password is accepted, use the ◄ key or the
► key to select the menu subsection that contains the
parameter you would like to change: Unit, Cooling,
Compressor Systems, Supply System, Heating, Econo-
mizer, Ventilation, or Exhaust. The setpoints contained
under each of these menu subsections and their pass-
through
. Use the ▼ key and the
▲ key to navigate to the parameter to change. Follow
to change the value.
PROGRAM
All PROGRAM information is User Enabled/User Dis-
abled values. Program parameters can be viewed under
their respective menu select key on the left side of the
keypad. However, they can only be changed under the
PROGRAM key using the following procedure.
Press the PROGRAM key to enter the menu. The Enter
Password screen appears. All program parameters re-
quire the use of a password before they can be changed.
for information
on how to enter a password into the UI. When a Level 1
password is entered, only Level 1 program information
is available to change. Entering a Level 2 password
makes all program information available.
After the password is accepted, use the ◄ key or the ►
key to select the menu subsection that contains the pa-
rameter to change: Unit, Cooling, Compressor Systems,
Supply System, Heating, Economizer, Ventilation, or
Exhaust. The parameters contained under each of these
menu subsections and their password level are contained
in
through
. Use the ▼ key and the ▲ key to navigate to the
parameter to change. Follow the instructions given in
the section
to change the
parameter to the desired value.
OPTIONS
All OPTIONS information is selected from the listed
parameter data. Options parameters can be viewed un-
der their respective menu select key on the left side of
the keypad. However, they can only be changed under
the OPTIONS key using the following procedure.
Press the OPTIONS key to enter the menu. The Enter
Password screen appears. All options parameters re-
quire the use of a password before they can be changed.
tion on how to enter a password into the UI. When
a Level 1 password is entered, only Level 1 options
information is available to change. Entering a Level 2
password makes all options information available.
After the password is accepted, use the ◄ key or the
► key to select the menu subsection that contains the
parameter to change: Unit, Cooling, Compressor Sys-
tems, Supply System, Heating, Economizer, Ventila-
tion, or Exhaust. The parameters contained under each
of these menu subsections and their password level are
contained in
through
. Use the ▼ key and the ▲ key to navi
-
gate to the parameter to change. Follow the instruc-
to change the parameter to the desired value.
DATE / TIME
To change the day, time, and date, press the DATE/
TIME key. The ▼ key is used to scroll to the next item
to be programmed and the ▲ key scrolls to the previ
-
ous item. The following messages are displayed. The
first line is an active display and the second line is the
entry line.
CLOCK FRI 18 JUN 2004 10:15:33 AM
DAY OF MONTH =XX
CLOCK FRI 18 JUN 2004 10:15:33 AM
MONTH =XX
CLOCK FRI 18 JUN 2004 10:15:33 AM
YEAR =XXXX
CLOCK FRI 18 JUN 2004 10:15:33 AM
HOUR =XX
CLOCK FRI 18 JUN 2004 10:15:33 AM
MINUTE =XX