SECTION 5 – SEQUENCE OF OPERATION
TABLE 20 -
CURRENT OPERATING MODE
CURRENT OPERATING MODE
UNIT TYPE
DESCRIPTION
Occ Standby
ALL
There is no demand for cooling, heating, or dehumidification
Occ Cooling
VAV
There is a demand for cooling
Occ Cooling Low
SZVAV
There is a demand for low cooling
Occ Cooling High
SZVAV
There is a demand for high cooling
Occ Cooling without Bypass
FlexSys
There is a demand for cooling
Occ Cooling with Bypass
FlexSys
There is a demand for cooling
Occ Heating
VAV or FlexSys
There is a demand for heating
Occ Heating Low
SZVAV
There is a demand for low heating
Occ Heating High
SZVAV
There is a demand for high heating
Unocc Standby
ALL
There is no demand for cooling, heating, or dehumidification
Unocc Cooling
VAV or FlexSys
There is a demand for cooling
Unocc Cooling Low
SZVAV
There is a demand for low cooling
Unocc Cooling High
SZVAV
There is a demand for high cooling
Unocc Heating
VAV or FlexSys
There is a demand for heating
Unocc Heating Low
SZVAV
There is a demand for low heating
Unocc Heating High
SZVAV
There is a demand for high heating
Comfort Ventilation Cooling
SZVAV
There is a demand for cooling
Comfort Ventilation Heating
SZVAV
There is a demand for heating
Morning Warm-Up
ALL
There is a demand for heating
Occ Dehumidification with Cooling
VAV or SZVAV
There is a demand for dehumidification
Occ Dehumidification Cool Low
VAV or SZVAV
There is a demand for low dehumidification
Occ Dehumidification Cool High
VAV or SZVAV
There is a demand for high dehumidification
Unocc Dehumidification with Cooling
VAV or SZVAV
There is a demand for dehumidification
Unocc Dehumidification Cool Low
VAV or SZVAV
There is a demand for low dehumidification
Unocc Dehumidification Cool High
VAV or SZVAV
There is a demand for high dehumidification
SINGLE ZONE VAV (SZVAV)
• An HVAC system that has no VAV boxes installed
in the duct work operates as SZVAV.
•
A SZVAV configured unit has a supply fan con
-
trolled by a VFD that is capable of running at dif-
ferent speeds according to a cooling/heating de-
mand or supply fan only demand.
• Series 100 units ordered as SZVAV do not have a
duct static pressure transducer installed.
•
SZVAV configured units do not have the ability to
control duct static pressure and have no high duct
static pressure protection.
• SZVAV units can be controlled by either a stan-
dard thermostat (staged) input or a zone tempera-
ture input.
SZVAV Setup
• Unit type must be set to SZVAV in the OPTIONS-
UNIT DATA
menu.
• Zone control method must be set in the
PRO-
GRAM-UNIT DATA menu.
• Single zone VAV minimum VFD speed must be
set in the SETPOINTS-SUPPLY SYSTEM menu.
•
Unit design airflow must be set in the
SET-
POINTS-UNIT DATA menu.
• Occ zone cooling setpoint must be set in the SET-
POINTS-COOLING menu (zone control method
is Wired or Comm Zone Temperature).
• 1st and 2nd stage cooling setpoints must be set in
the SETPOINTS-COOLING menu.