SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
7
ECONO INSTALLED
This parameter is programmed through the PROGRAM key and tells the IPU board what type
of economizer is installed, None, Dry Bulb, Single Enthalpy, Dual Enthalpy.
ECONO METHOD
ACTIVE
This value indicates which of the available economizer methods the IPU board is using.
ECONO METHOD TO
USE
This parameter is programmed through the PROGRAM key and tells the IPU board which
of the available economizer options to use. The choices are Dry Bulb, Single Enthalpy, Dual
Enthalpy, or Best Available.
ECONO OUTPUT FOR
FAN START
This parameter is set through the SETPOINTS key and identifies the position of the
economizer damper required to turn ON the exhaust fan in an ON/OFF DAMPER CTRL.
ECONO OUTPUT FOR
FAN STOP
This parameter is set through the SETPOINTS key and identifies the position of the
economizer damper required to turn off the exhaust fan in an ON/OFF DAMPER CTRL option.
ECONO SYS STATUS
This is the active status of the economizer system, display will show Normal- Active, Normal-
Inactive, Faulted, User Disabled; or None.
ELEC HEAT CAPACITY
This parameter is programmed through the OPTIONS key. This parameter is used to identify
the electric heat capacity installed in the unit. The options are 40 KW, 80 KW, 40 KW-200, 80
KW-200, 100 KW, 100 KW-200, 108 KW, 120 KW, 150 KW, 160 KW, 200 KW, 240 KW, or 250
KW.
EVAP LEAVING AIR
TEMP HIGH
This parameter is programmed through the SETPOINTS key. This becomes the Active Supply
Air Temperature Setpoint for a FlexSys unit when it is in the Occupied Cooling With Bypass
mode.
EVAP LEAVING AIR
TEMP LOW
This parameter is programmed through the SETPOINTS key. This becomes the Active Supply
Air Temperature Setpoint for a FlexSys unit when it is in the Dew Point Reset mode.
EXHAUST DAMPER
POSITION/VFD
This identifies the percentage output from the IPU board to the Exhaust Damper or Exhaust
Fan when controlled by the unit or BAS (when exhaust Control BAS is enabled).
EXHAUST FAN OUTPUT
This identifies the IPU board is sending a Binary output to energize the exhaust fan circuit.
EXHAUST FAN STATUS
This verifies a Binary input to the IPU board is present when the exhaust fan is operating.
EXHAUST OUTPUT FOR
FAN START
This parameter is set through the SETPOINTS key and identifies the position of the exhaust
damper required to turn ON the exhaust fan in an ON/OFF PRESS CNTRL option.
EXHAUST OUTPUT FOR
FAN STOP
This parameter is set through the SETPOINTS key and identifies the position of the exhaust
damper required to turn off the exhaust fan in an ON/OFF PRESS CNTRL option.
EXHAUST/RETURN FAN
VFD
This is a derived value that indicates the output, in percent, to the Return Fan VFD.
EXHAUST SYS STATUS
This is the active status of the exhaust system. The display will show Normal-Active, Normal-
Inactive, Faulted, User Disabled, or None.
EXHAUST/RETURN FAN
VFD
This identifies speed output in percentage that is being sent to the exhaust or return fan VFD.
FAN SPEED SETP FOR
HIGH SAT
This parameter is programmed through the SETPOINTS key. When the supply fan speed is
equal to or less than this value the Active Supply Air Temperature Setpoint on a Variable Air
Volume Unit is set to the SAT Setpoint High Limit.
FAN SPEED SETP FOR
LOW SAT
This parameter is programmed through the SETPOINTS key. When the supply fan speed is
equal to or greater than this value the Active Supply Air Temperature Setpoint on a Variable Air
Volume Unit is set to the SAT Setpoint Low Limit.
FILTER STATUS
This is status of the unit filters. A differential pressure switch must be installed to measure the
pressure drop across the filters. When the filters are dirty the switch closes sending a Binary
signal to the IPU board. The User Interface display will show Okay or Change.
FLEX EVAP TEMP
ACTIVE SP
This is the active evaporator temperature setpoint that the IPU board is trying to control to. This
value is used when a FlexSys unit is in the Occupied Cooling With Bypass mode.
FLEX EVAP TEMP
CURRENT
This is the actual air temperature leaving the evaporator coil of a FlexSys unit.
FURNACE 1 MODE
This is the current status of the first heat exchanger section of a staged gas heat unit. The
User Interface will display Off, Purge, Ignition, On-Low, On-High, Safety Trip, Safety Fault,
Safety Lockout, or Fault- I/O.
TABLE 54 –
DEFINITIONS (CONT'D)