JOHNSON CONTROLS
122
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
SECTION 6 – USER INTERFACE CONTROL CENTER
TABLE 46 –
HEATING (CONT'D)
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SETTING
LOCATION
SHOW WHEN UNIT TYPE IS
HW / STEAM
VALVE POS
0–100%
Derived
Heat Type Equals Hot Water
Heat Steam
FRZ STAT
Ok Tripped
Derived
HEATING CONTROL
OFFSET
1.0°F To 100.0°F
Derived
MOD FURNACE OUTPUT
RELATIVE
0–100%
Derived
Heat Type Equals Modulating
Gas
APRX RATE
37.5–900.0 Mbh
Derived
FURNACE 1A MODE
Off / Purge / Ignition
/ On - Low /
On - High / Safety
Trip / Safety Fault
/ Safety Lockout /
Fault - L/O
Derived
Heating Type Equals
Modulating Gas
FURNACE 1A MODE
RELATIVE
0–100%
Derived
Heat Type Equals Modulating
Gas
APRX RATE
37.5–150.0 Mbh
Derived
FURNACE 1B MODE
Off / Purge / Ignition
/ On / Safety Trip /
Safety Fault / Safety
Lockout / Fault -L/O
Derived
Heat Type Equals Modulating
Gas
FURNACE 1 MODE
Off / Purge / Ignition
/ On-Low / On -
High / Safety Trip /
Safety Fault / Safety
Lockout / Fault -L/O
Derived
Heat Type Equals Staged Gas
FURNACE 2 MODE
Off / Purge / Ignition
/ On - Low /
On - High / Safety
Trip / Safety Fault
/ Safety Lockout /
Fault -L/O
Derived
Gas Heat Size Equals 750
MBH Or 1125 MBH
FURNACE 3 MODE
Off / Purge / Ignition
/ On - Low /
On -High / Safety
Trip / Safety Fault
/ Safety Lockout /
Fault -L/O
Derived
Gas Heat Size Equals 1125
MBH
HEATING SYSTEM
1
User Enabled User
Disabled
User
Enabled
Program / Heating
Heat Type Does Not Equal
None
MORNING WARM UP
1
User Enabled User
Disabled
User
Disabled
Program / Heating
Heat Type Does Not Equal
None And Constant Volume
Control Method Does Not
Equal Staged