SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
6
SERVICE
To enter Service mode, press the SERVICE key. The
following message initially displays when the SER-
VICE key is pressed unless a Level 2 password is ac-
tive.
SERVICE
ENTER PASSWORD
All the DIGITAL outputs, except for the compressors,
can be forced ON. In order to force the outputs, the lo-
cal stop switch must be in the OFF position. To force
an output ON, use the ◄ or ► key to navigate to the
SERVICE digital outputs section. Then use the ▲ or
▼ key to select the output to force ON. Press the
key and then use the ► key to switch it from OFF to
ON. Press the
key again to energize the output. Re-
peat the above process in reverse to turn the forced out-
put back to OFF.
All the ANALOG outputs can be forced ON. In order
to force the outputs, the local stop switch must be in
the OFF position. To force an output ON, use the ◄
or ► key to navigate to the SERVICE analog outputs
section. Then use the ▲ or ▼ key to select the output
you want to force ON. Press the
key and then use
the numeric keypad to enter the output value. Press the
key again to energize the output. Repeat the above
process in reverse to turn the forced output back to 0.0.
Failure to revert the forced output back to 0.0 leaves
the forced output value in place until a different value
is initiated by the operation of the unit
.
The ► key can be used to jump to the beginning of the
next section of displays, and the ◄ key can be used to
jump to the beginning of the previous section of dis-
plays.
The sections of displays are as follows:
• Parameters
• Analog inputs
• Digital inputs
• Digital outputs
• Analog outputs
lists the displayed text, input or
output type, IPU board terminal location (ID), value
range, and when the item is displayed.
The following is an example of an analog input display
that can be viewed from Service mode. See
for a listing of the analog inputs.
SERVICE AI PIO J07-01 XX.X VDC
+ BUILDING STATIC PRES =XX.XXINWC
Following is an example of a digital input display that
can be viewed from Service mode. See
for a listing of the digital inputs.
SERVICE DI PIO TB08-01
LOCAL STOP RUN
Following is an example of a digital output display
that can be viewed from Service mode. The XXX is
replaced with OFF or ON in this section. See
for a listing of the digital outputs.
SERVICE DO PIO TB03-05
COMPRESSOR 2A OFF
Following is an example of an analog output display
that can be viewed from Service mode. See
for a listing of the analog outputs
SERVICE AO PIO TB08-01 XX.X VDC
+ SYS 1 FEED VALVE OUTPUT =XXX.X %