SECTION 6 – USER INTERFACE CONTROL CENTER
BACNET
NAME
USER INTERFACE
NAME
READ/
WRITE
BACNET
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
FURN_OUT_5
Elect Heat Stage 5
Status Staged Gas
Furn 3 Low Status
Mod Gas Furn 3
Low Status
R
BI30
1311
Displays The Status Of The Control Output
To The Indicated Heat Section: 0=Off
1=On
FURN_OUT_6
Elect Heat Stage 6
Status Staged Gas
Furn 3 High Status
Mod Gas Furn 3
High Status
R
BI31
1312
Displays The Status Of The Control Output
To The Indicated Heat Section: 0=Off
1=On
FURN_OUT_7
Elect Heat Stage
7 Status Mod Gas
Furn 1B Status
R
BI32
1313
Displays The Status Of The Control Output
To The Indicated Heat Section: 0=Off
1=On
HEAT_ENABLE
Heating System
R/W
AV83 BV07
1108
A BAS Command That Allows The Heating
Function To Be Turned On/Off: 0=Enabled
1=Disabled
HEAT_ENT_
TEMP
Heat Entering Temp
R
AI22
535
Displays The Actual Temp Of The Air
Entering The Elect, Staged Gas, Or Mod
Gas Heat Sections
HEAT_STAGES
Electric Heat Stages
Or Gas Heat Stages
R
AI23
536
Displays The Number Of Elect Or Staged
Gas Heat Stages Available
HEAT_
VACTION
Hw Valve Action
R/W
AV84 BV08
1109
A BAS Command That Allows The Hot
Water/Steam Valve Action To Be Changed:
0=Direct 1=Reverse
HEATING_SAT
Heating Suppy Sir
Temp Sp (VAV Or
FlexSys)
R/W
AV09
1034
Displays The Active Supply Air Temp Sp
For Heating
HEATING_VLV
Heating Valve
R
AI24
537
Displays The Ouput From The Control To
A Hw/Steam Valve Or Mod Gas Heat Valve
(%)
HW_FRZ_STAT
Hw/Steam Coil
Freezestat Status
R
BI33
1314
Displays The Status Of The Freezestat On
Units With Hw/Steam Heat: 0=No Fault
1-Faulted
LOCAL_STOP
Local Stop Status
R
BI34
1315
Displays The Status Of The 24Vac Input
To The Control Board Through The SD
Terminal And/Or The Unit On/Off Switch
MAX_BYPASS
Maximum Bypass
Sp (FlexSys)
R/W
AV10
1035
Displays The Max Setting For The Bypass
Damper
MAX_FLOW_
DV
Outside Air Max
Flow Sp
R/W
AV11
1036
Displays The Max Airflow For Demand
Ventilationwith An Airflow Station (CFM)
MECH_LCK_
TMP
Mech Cooling
Lockout Sp
R/W
AV12
1037
Displays The Min OA Temp At Which Mech
Cooling Is Allowed To Operate
MIN_FLOW_DV
Outside Air Min
Flow Sp
R/W
AV13
1038
Displays The Min Airflow For Demand
Ventilation With An Airflow Station (CFM)
TABLE 53 –
BACNET MS/TP, MODBUS, BACNET IP (SEE NOTES AT END OF TABLE) (CONT'D)