SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
6
DISPLAY TEXT
TYPE
ID
VALUE RANGE LOCATION
DESCRIPTION
CO2 LEVEL
INSIDE
Analog
Input
J5-3
0-5 Volts
I/O Board
Analog Input From The Indoor CO
2
Sensor
RETURN FAN PRESS
CURRENT
Analog
Input
J6-1
0-5 Volts
I/O Board
Analog Input From The Return Fan
Pressure Transducer
DUCT STATIC PRESS
CURRENT
Analog
Input
J6-2
0-5 Volts
I/O Board
Analog Input From The Supply Air
Pressure Transducer
BUILDING PRESSURE
CURRENT
Analog
Input
J6-3
0-5 Volts
I/O Board
Analog Input From The Building
Pressure Transducer
OA FLOW INPUT 1
Analog
Input
J6-4
0 To 4095 A/D
Counts (1-5
Volts)
I/O Board
This Is The Air Flow Input From The Tek
Air Measuring Station
OA FLOW INPUT 2
Analog
Input
J6-5
0 To 4095 A/D
Counts (1-5
Volts)
I/O Board
This Is The Air Flow Input From The Tek
Air Measuring Station
OA FLOW PRESSURE 1
Analog
Input
J6-4
0 To 0.25" W.C.
(0-5 Volts)
I/O Board
Analog Input From The Air Measuring
Station Pressure Transducer
OA FLOW PRESSURE 2
Analog
Input
J6-5
0 To 0.25" W.C.
(0-5 Volts)
I/O Board
Analog Input From The Air Measuring
Station Pressure Transducer
OA FLOW VELOCITY 1
Analog
Input
J6-4
0 To 2002 Fpm
(0-5 Volts)
I/O Board
Analog Input From The Air Measuring
Station Pressure Transducer
OA FLOW VELOCITY 2
Analog
Input
J6-5
0 To 2002 Fpm
(0-5 Volts)
I/O Board
Analog Input From The Air Measuring
Station Pressure Transducer
ZONE TEMP CURRENT
Analog
Input
J7-1
0-5 Volts
I/O Board
Analog Input From The Zone
Temperature Sensor
UNDERFLOOR SLAB
TEMP
Analog
Input
J7-2
0-5 Volts
I/O Board
Analog Input From The Under Floor
Temperature Sensor
UNDERFLOOR AIR
HUMIDITY
Analog
Input
J7-3
0-5 Volts
I/O Board
Analog Input From The Underfloor
Humidity Sensor
SUPPLY AIR
TEMP RST
Analog
Input
J7-4
0-5 Volts
I/O Board
Hardwired Analog Input To Reset The
Supply Air Temperature Setpoint
DUCT STATIC
PRES RESET
Analog
Input
J7-5
0-5 Volts
I/O Board
Hardwired Analog Input To Reset The
Duct Static Pressure Setpoint
FURNACE STATUS
Analog
Input
J5-1
0-5 Volts
I/O Board
Analog Input Of The Furnace
Multiplexer
FURNACE 1A
STAT HI
Digital
Input
TB01-3
On / Off
Furnace
Multiplexer
Furnace 1A Hz Status Input To Furnace
Multiplexer Board
FURNACE STATUS
COUNTS
Analog
Input
J5-1
0 - 4095
I/O Board
Status Of The Input From The Furnace
Multiplexer Board In Count
FURNACE 1 STATUS
Digital
Input
TB01-2
On / Off
Furnace
Multiplexer
Furnace 1 Status Input To Furnace
Multiplexer Board
FURNACE 1A STATUS
Digital
Input
TB01-2
On / Off
Furnace
Multiplexer
Furnace 1A Status Input To Furnace
Multiplexer Board
FURNACE 1B STATUS
Digital
Input
TB01-6
On / Off
Furnace
Multiplexer
Furnace 1B Status Input To Furnace
Multiplexer Board
FURNACE 2 STATUS
Digital
Input
TB01-3
On / Off
Furnace
Multiplexer
Furnace 2 Status Input To Furnace
Multiplexer Board
FURNACE 3 STATUS
Digital
Input
TB01-4
On / Off
Furnace
Multiplexer
Furnace 3 Status Input To Furnace
Multiplexer Board
TABLE 51 –
SERVICE (CONT'D)