SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
TABLE 54 –
DEFINITIONS (CONT'D)
CONTROL METHOD
This parameter is programmed through the OPTIONS key and identifies the control method
being used on a Constant Volume unit. The choices are Staged, Wired Zone Temp or Comm
Zone Temp.
COOLING CONTROL
OFFSET
This is the control band the unit is trying to maintain. The control band is the Active Se/-
the Cooling Control Offset. If the temperature is above this band additional cooling is required,
if the temperature is below this band cooling is decreased.
CURRENT OPER MODE
This is the current operating mode of the unit. The display will show OCC Standby, OCC
Cooling Low, OCC Cooling High, OCC Heating Low, OCC Heating High, UNOCC Standby,
Unnocc Cooling Low, UNOCC Cooling High, UNOCC Heating Low, UNOCC Heating High,
Morning Warm-up, Comfort Vent Cooling, Comfort Vent Heating, Occupied Cooling, Occupied
Heating, Unoccupied Cooling, Unoccupied Heating, OCC Cooling W/O Bypass, OCC Cooling
W Bypass, or Underfloor Temp Override.
CURRENT RUN TIME
COMP A
This is the amount of time the compressor has been in operation during the current cycle. This
is shown for each compressor of every compressor system.
CURRENT RUN TIME
COMP B
This is the amount of time the compressor has been in operation during the current cycle. This
is shown for each compressor of every compressor system.
DAILY WARM UP TIME
This is the time it takes to bring the Return Air Temperature up to setpoint during Adaptive
Morning Warm Up. The IPU board uses this value in the calculation of Daily Warm Up Time
Day 1.
DAILY WARM UP TIME
DAY 1
This is the Morning Warm Up time the IPU board recorded during the previous day 1. This
value is used to calculate the current Morning Warm initiate time for Adaptive Morning Warm
Up.
DAILY WARM UP TIME
DAY 2
This is the Morning Warm Up time the IPU board recorded during the previous day 2. This
value is used to calculate the current Morning Warm initiate time for Adaptive Morning Warm
Up.
DAILY WARM UP TIME
DAY 3
This is the Morning Warm Up time the IPU board recorded during the previous day 3. This
value is used to calculate the current Morning Warm initiate time for Adaptive Morning Warm
Up.
DAMPER HARDWARE
This parameter is programmed through the OPTIONS key and identifies the type of ventilation
system installed in the unit. The choices are None, 2 Position Damper, Standard Dampers,
TEK-AIR.
DEW POINT RESET
This parameter is programmed through the PROGRAM key. This function changes the Active
Supply Air Temperature to a lower value when the air beneath the floor of a FlexSys unit
approaches the dew point temperature of the air. The choices are USER ENABLED or USER
DISABLED.
DISPLAY LANGUAGE
This parameter is programmed through the OPTIONS key. This allows the user to select the
language the IPU board will use to display the information at the User Interface. The choices
are English or Spanish.
DISPLAY UNITS
This parameter is programmed through the OPTIONS key. This allows the user to select which
unit of measure the IPU board will use to display the information at the User Interface. The
choices are Imperial, metric.
DUCT PRESS
TRANSDUCER SPAN
This parameter is programmed through the SETPOINTS key. This allows the use of three
different duct pressure control ranges, 0 to
1.00 in-wg
, 0 to
2.50 in-wg
, or 0 to
5.00 in-wg
.
DUCT STATIC OVER
PRESSURE
This parameter is programmed through the SETPOINTS key. This sets the maximum allowable
Duct Static value before the IPU board lockouts the unit on an over pressure fault.
DUCT STATIC PRESS
ACTIVE SP
This is the current Duct Static Setpoint that the IPU board is trying to maintain.
DUCT STATIC PRESS
CURRENT
This is the actual duct static pressure value.
DUCT STATIC RESET
LOW SETP
This parameter is programmed through the SETPOINTS key. This is the minimum Duct Static
Control point.
DUCT STATIC RESET
HIGH SETP
This parameter is programmed through the SETPOINTS key. This is the maximum Duct Static
Control point.
ECONOMIZER CONTROL
OUTPUT
This is the analog output from the IPU board to the Economizer Damper Actuator.