JOHNSON CONTROLS
21
SECTION 2 – INSTALLATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
2
TABLE 3 -
PHYSICAL DATA (CONT'D)
70 TON MODELS
MODEL SIZE
070
Optional Exhaust Fan
Quantity Fans/Motors
2 / 1
Type
FC
Size
20-18
Motor Size Range (min. to max. HP, total
for two fans))
5–30
Airflow Range (min. to max. CFM)
4000–36000
Static pressure range (min. to max. IWG)
0–2”
Optional Return Fan
Quantity Fans/Motors
2 / 2
Type
Plenum
Size
270
Motor Size Range (min. to max. HP, total
for two fans))
10–30
Airflow Range (min. to max. CFM)
4000–32000
Static pressure range (min. to max. IWG)
0-3”
Evaporator Coil
Size (square feet)
56.9
Number of rows / fins per inch
4/17
Tube Diameter / Enhanced Surface
3/8"/Enhanced
Condenser Coil
Size (square feet)
164
Number of rows / fins per inch
1/21
Tube Diameter / Surface
1 mm/
microchannel
Condenser Fans
Quantity
6
Type
Prop.
Diameter (inches)
36
Power (HP each)
2
Filters - 2” Throwaway (Pre-Filter Position)
Quantity
10 / 15
Size (length x width) (in.)
25x16 / 25x20
Total Filter Face Area (square feet)
77.1
Filters - 2” Cleanable (Pre-Filter Position)
Quantity
10 / 15
Size (length x width) (in.)
25x16 / 25x20
Total Filter Face Area (square feet)
77.1
Filters - 2” Pleated, 30% Efficient (Pre-Filter Position)
Quantity
10 / 15
Size (length x width) (in.)
25x16 / 25x20
Total Filter Face Area (square feet)
77.1
Filters -12” Rigid 65%, 2” 30% Prefilter (Pre-Filter Position)
Quantity
2 / 8 / 9
Size (length x width) (in.)
16x20 /
25x16 / 25x20
Total Filter Face Area (square feet)
55.8
MODEL SIZE
070
Filters -12” Rigid 95%, 2” 30% Prefilter (Pre-Filter Position)
Quantity
2 / 8 / 9
Size (length x width) (in.)
16x20 /
25x16 / 25x20
Total Filter Face Area (square feet)
55.8
Filters - 2” Carbon (Pre-Filter Position)
Quantity
10 / 15
Size (length x width) (in.)
16x20 /
25x16 / 25x20
Total Filter Face Area (square feet)
77.1
Filters - 12” rigid 95% in Post-filter Position
Quantity
2 / 7 / 9
Size (length x width) (in.)
16x20 /
25x16 / 25x20
Total Filter Face Area (square feet)
55.1
Gas Furnace
Staged Furnace Sizes
(input/output/stages)
375 mbh / 300
mbh / 2 stages
750 mbh / 600
mbh / 4 stages
1125 mbh / 900
mbh / 6 stages
Inlet Gas Pressure Range
(min. to max. IWG)
Natural 4.5–10.5” w.c.
Propane 11.0–13.0” w.c.
Airflow Range (min. to max. CFM)
6,950–36,000
Modulating Furnace Sizes
(input/output/turndown)
375 mbh /
300 mbh / 8:1
turndown
750 mbh / 600
mbh / 16:1
turndown
1125 mbh /
900 mbh /
24:1 turndown
Inlet Gas Pressure Range
(min. to max. IWG)
Natural 4.5–10.5” w.c.
Propane 11.0–13.0” w.c.
Minimum Heat Exchanger Entering SAT
40.0 °F
Airflow Range (min. to max. CFM)
8,250–36,000
Electric Heaters
Size Range (min. to max. kW)
80–200
Heating Steps
1
2–6
Minimum OAT For Mech. Clg.
45
Low Ambient Option Min. OAT
0
1.
Electric heat steps and airflow range depends on voltage and
size. Consult the air pressure drop tables for specific number
of steps for a given voltage.
2. Weights are for components only and need to be added to the
extended cabinet weights. The diffuser is required in the ex-
tended cabinet for any unit with hot water or final filter option.