7.14 Security contact autotest function
Model
All
Associated
parameters
ID
Description
Type
P5E...P77 IN
XX
INPUT
P78...P7C OUT
XX
OUTPUT
P54...P5C Switch
X
SWITCH
P48
Autotest max attempt
NUMERIC
Associated errors
ID
Description
Type
Er19
Test closing error
Error
Er20
Test opening error
Error
Description
The security contact autotest function allows automatically test the connected security
contacts before every opening and closing maneuvers to ensure that they are correctly
working.
Configuration
System set-up:
In order to use security contact autotest function on VERSUS control
panels the security contact must be supplied by control panel voltage output.
Depending on the control panel model this output can be 12Vdc or configurable
12/24Vdc. The security contact output it must be connected to the corresponding
control panel input.
Parameters:
The output that supplies the security contact must be configured as a
“Autotest signal” if the security contact is used for closing and opening maneuvers. This
configuration can be done by means of
P78
to
P7C
configuration parameters by using
a VERSUS-PROG programming tool. For the security contact signal input it must be
configured as “SEC.CL autotest” in case of closing maneuver or “SEC.OP autotest” in
case of opening maneuvers. This configuration can be done by means of
P5E
to
P77
configuration parameters.
Summary of Contents for GAMMA VERSUS M20
Page 7: ...GAMMA VERSUS MANUAL 7 COD 1257066 Gamma VERSUS Manual v1 13 2 5 Rolling door 2 6 Fast door...
Page 75: ...GAMMA VERSUS MANUAL 75 COD 1257066 Gamma VERSUS Manual v1 13...
Page 78: ...GAMMA VERSUS MANUAL 78 COD 1257066 Gamma VERSUS Manual v1 13...
Page 79: ...GAMMA VERSUS MANUAL 79 COD 1257066 Gamma VERSUS Manual v1 13...