94
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
1) r/w = read/write
Table 5, read energy
Energy in integer format
Energy
Address
(dez)
r/w
1)
Format Unit
Comment
Real energy consumption, T10
9000
r
long
Wh
scale see address 9102
Real energy supply, T30
9001
r
long
Wh
scale see address 9102
Real energy without rev. run. stop, T50 9002
r
long
Wh
scale see address 9102
Reactive energy capacitive, T20
9003
r
long
varh scale see address 9102
Reactive energy inductive, T10
9004
r
long
varh scale see address 9102
React. energy without rev. run. stop T40 9005
r
long
varh scale see address 9102
Running time of energy meters
7600
r
date[6][5]
sec.
Running time in seconds
Format of time information: date {unsign. long}
Table 6, delete energy
Description
Address
(dez)
r/w
1)
Format
Unit
Comment
Delete real energy
576
w
word
1=delete
Delete reactive energy
578
w
word
1=delete
Delete maximum values
580
w
word
1=delete
Delete minimum values
582
w
word
1=delete
Table 8, EMAX-maximum values
EMAX-maximum values
Description
Address
(dez)
r/w
1)
Format
Comment
Real power EMAX
Peak value
16000
r
float [Tariff] [Month]
Measured value in Watt.
Date
Year
16500
r
char [Month]
In which year the month was.
Day
16600
r
char [Tariff] [Month]
On which day of the month the
peak value ocurred.
Time
Hour
16700
r
char [Tariff] [Month]
Minute
16800
r
char [Tariff] [Monat]
For each month, one peak value is saved per tariff. After one year, the peak value is overwritten.
Year
= 0 .. 99
00 .. 99 = 2000 .. 2099
Tariff
= 0 .. 4
0 = T00, 1 = T01, ..
Month = 0 .. 11
0 = January, 1 = February, ..
Table 7, energy
Energy in floating point format
Description
Address
(dez)
r/w
1)
Type
Unit Comment
Real energy consumption
2000
r
double[5]
Wh
Energy, T00 .. T04
Reactive energy inductive
2010
r
double[5]
varh
Energy, T10 .. T14
Reactive energy capacitive
2020
r
double[5]
varh
Energy, T20 .. T24
Real energy supply
2030
r
double[5]
Wh
Energy, T30 .. T34
React. energy without rev. run. stop
2040
r
double[5]
varh
Energy, T40 .. T44
Real energy without rev. run. stop
2050
r
double[5]
Wh
Energy, T50 .. T54