61
= Key1
= Key 2
= Key 3
= Max. value or consumption = Min. value or supply
Generator control
The
Run up time
is here the time, which the
generator needs to supply its power after switching
on.
The
minimum running time
is the time, which the
generator must run, before it can be disconnected
again by the UMG 505.
The
speed,
with what the analogue signal is chan-
ging, is 2% of the difference from maximum
connection power less minimum connection power
per second. The
speed
cannot be changed directly.
Consumer control
The
run up time
sets a limit to the starting speed of
the consumer’s power. To reach maximum
connection power from minimum connection power
takes the run up time.
The
maximum spare power
represents the power,
that may be spared within one measuring period.
EMAX analogue
output
Maximum connection
power
Generator
Minimum connection
power
Priority
EMAX analogue
outputs
Maximum connection
power
Consumer
Minimum connection
power
Priority
EMAX analogue
output
Max. spare power
Run up time
Priority
Max.
connection po-
wer
Min. connection
power
Run up time
Run up time
Consumer power
t
P
EMAX analogue po-
wer
Minimum running
time
Run up time
Priority
W
W
CONF
CONF
CONF
W
W
W
CONF
Description
Setting range
Priority
: 0 .. 9 (0 = off)
EMAX analogue output
: 1 .. 4
Max. connection power
: 0W .. 9999MW
Min. connection power
: 0W .. 9999MW
Max. spare power
: 0W .. 9999MW
Run up time
: 10 .. 9999sec.
Description
Setting range
Priority
: 0 .. 9 (0 = off)
EMAX analogue output
: 1 .. 4
Max. connection power
: 0W .. 9999MW
Min. connection power
: 0W .. 9999MW
Minimum running time
: 0 .. 9999minutes
Run up time
: 0 .. 99sec.
Min. running time
Maximum
connection po-
wer
Minimum
connection po-
wer
Generator power
t
„analogue
output“
„digital output“
On
Of
Run up time
t
20mA