Activate energy meter
In UMG505 up to 30 energy meters are at your
disposal. The 6 energy meters Tx0 can only be
deleted, but not deactivated. The other 24 energy
meters can be deactivated. Only active energy
meters count the occurred energy. The changeable
energy meters are marked grey in the following dia-
gram.
The changeover of the energy meters is carried out
via the input channels 1-16 or via the switching
clock. An energy meter is active, when it is activated
via an input channel
or
the switching clock.
Changeover of EMAX targ. val. (Option)
For the EMAX program, up to 5 targets can be va-
lid. If not otherwise programmed, target 1 is active.
Via the
input channels
1-16 and via the switching
clock, one of the 5 targets can be selected and
assigned to the EMAX program.
If the target is activated via the input channels, and
another target simultaneously by the switching
clock, the target with the highest target number is
used by the EMAX program.
Energy meter
Fix Changeable
Real energy
without rev. run. stop
T50 T51 T52 T53 T54
Consumption
T00 T01 T02 T03 T04
Supply
T30 T31 T32 T33 T34
Reactive energy
Without rev. run. stop T40 T41 T42 T43 T44
inductive
T10 T11 T12 T13 T14
capacitive
T20 T21 T22 T23 T24
Diagr. The energy meters of UMG 505.
EMAX target number
1 - 5
Activate energy meter
CONF
Input channel 0 - 15
EMAX target number
Activate energy meter
CONF
Input channel 1 - 16.